• Acceleration/deceleration time:
It is advisable to set the acceleration and deceleration ramps to
more than 0.5 seconds. Ensure that the drive controller does not
exceed the current limit. A braking resistor should be used on
overhauling loads.
• Brake release time (brt):
Adjust according to the time required for the mechanical brake to
open.
• Brake engage frequency (bEN):
Set to twice the nominal slip (in the example above 2 x 0.0466 =
0.0932 Hz). Then adjust according to observed results.
• Brake engage time (bEt):
Adjust according to the time required for the mechanical brake to
close.
Loss of 4–20 mA Signal (APL)
The logic output is at state 1 if the signal on the 4–20 mA speed
reference input is less than 2 mA.
Frequency Threshold 2 Attained (F2A)
The logic output is at state 1 if the motor frequency is greater than or
equal to the frequency threshold set by the F2d parameter in the
2—Adjust menu.
Drive Thermal Threshold Attained (tAd)
The logic output is at state 1 if the drive thermal state meets or
exceeds the thermal threshold set by the dtd parameter in the
2—Adjust menu.
Using the Analog Outputs
The analog outputs on the drive controller and on the Analog I/O and
Digital I/O extension cards are current outputs. The minimum and