
© 1998–2003 Schneider Electric All Rights Reserved
Chapter 3—Diagnostics and Troubleshooting VVDED397047USR6/03
Procedure 3: Checking the Peripheral Equipment 06/2003
102
Procedure 3: Checking the Peripheral Equipment
The following equipment may need to be checked. Follow the
manufacturers’ procedures when checking this equipment.
1. A protective device, such as a circuit breaker, may have tripped or
a fuse may have blown.
2. A switching device, such as a contactor, may not be closing at the
correct time.
3. Conductors may require repair or replacement.
4. Connection cables to the motor or high resistance connections to
ground may need to be checked. Follow NEMA standard
procedure WC-53.
5. Motor insulation may need to be checked. Follow NEMA standard
procedure MG-1. Do not apply high voltage to U, V, or W. Do not
connect the high potential dielectric test equipment or insulation
resistance tester to the drive controller since the test voltages
used may damage the drive controller. Always disconnect the
drive controller from the conductors or motor while performing
such tests.
CAUTION
DIELECTRIC TESTS WHILE CONNECTED
Can Cause Equipment Damage
• Do not perform high potential dielectric tests on circuits while the
circuits are connected to the drive controller.
• Any circuit requiring high potential dielectric tests must be
disconnected from the drive controller prior to performing the test.
Failure to follow these instructions can result in injury or
equipment damage.
Kommentare zu diesen Handbüchern