VVDED397047USR6/03 Chapter 2—Menus
06/2003 4—Control Menu
55
Table 14: 4—Control Menu: Other Parameters
Parameter Code Description
Adjustment
Range
Factory
Setting
NOTE: If CRL is
set higher than
CRH, reverse
sense operation
will result (i.e.,
20 mA will equal
low speed and
4 mA will equal
high speed).
AI2 min Ref.-mA
AI2 Max. Ref-mA
CrL
CrH
CrL: Minimum value of the
signal on analog input AI2
CrH: Maximum value of the
signal on analog input AI2
CrL:
0–20 mA
CrH:
4–20 mA
CrL: 4 mA
CrH:
20 mA
These two parameters allow definition of the signal at AI2.
The input can be configured for 0–20 mA, 4–20 mA,
20–4 mA, among other possibilities.
AO min Val-mA
AO Max. Val-mA
AOL
AOH
Min. value of the signal on
output AO
Max. value of the signal output
on AO
0–20 mA
0–20 mA
0 mA
20 mA
These two parameters are used to define the output signal
on AO.
For example: 0–20 mA, 4–20 mA, 20–4 mA, etc.
These parameters are available only with the I/O extension card installed.
Menu
4
AI 2
(mA)
0
LSP
HSP
CrL CrH 20
Frequency
AO (mA)
0
Max.
AOL AOH 20
Parameter