Chapter 2—Menus VVDED397047USR6/03
4—Control Menu 06/2003
56
Save Ref Str
This function allows saving the
reference, either when the run
command is removed (RAM) or
when
NO-RAM-
EEP
NO
mains power is removed (EEP). When the motor is next
started, the reference speed will be the last saved
reference. In order for speed reference to be saved in EEP
mode, the run command cannot be present when re-
applying power.
NOTE: Save Reference is only available if LIs are assigned
to +Speed/-Speed.
KeypadCom. LCC
Allows command of the drive
controller via the keypad display.
No - Yes No
The STOP/RESET, RUN, and FWD/REV keys are active.
The reference speed is given by the LFr or LCU parameter
(see page 30). Only the freewheel stop, fast stop, and
stop by DC injection commands remain active at the
terminal strip. If the link between the drive controller and
keypad display is lost, the drive controller will trip on the
SLF fault (serial link fault). If this parameter is set to YES
prior to the request to return to Factory Settings, it will
remain set to YES after returning to Factory Settings.
Table 14: 4—Control Menu: Other Parameters
Parameter Code Description
Adjustment
Range
Factory
Setting