VVDED397047USR6/03 Chapter 2—Menus
06/2003 5—I/O Menu
61
Table 16 shows which functions can be assigned to relay output R2,
logic output LO, and analog output AO.
Table 16: Possible Assignments for Configurable Outputs
I/O Extension Card
Analog
Output
AO
Logic
Output
LO
Drive Controller without an I/O Extension Card
Relay
R2
Analog
Output
AO1
NO: Not assigned No assigned X X X
RUN: DriveRunning Drive controller running X X
OCC: Output Cont. Output contactor command X X
FTA: Freq Attain. Frequency threshold attained X X
FLA: HSP Attained High speed attained X X
CTA: I Attained Current level attained X X
SRA: FRH Attained Reference speed attained X X
TSA: Mtr Therm Lv1 Motor thermal level attained X X
tAd: ATV th. alarm Drive thermal level attained X X
APL:4-20 mA loss Loss of 4–20 mA signal X X
F2A:F2 Attained
Second frequency threshold
reached
XX
BLC: Brk Logic
[1]
Brake logic X
OCR: Motor current Motor current X
OFR: Motor Frequency Motor speed X
ORP: Output Ramp Ramp output X
TRQ: Motor torque
[1]
Motor torque X
STQ: Signed Torq.
[1]
Signed motor torque X
ORS: Signed ramp Ramp output with +/– sign X
OPS:PI ref.
PI setpoint output, if one AI is
assigned to PIF
X
OPF:PI Feedback
PI feedback output, if one AI is
assigned to PIF
X
OPE:PI Error
PI error output, if one AI is
assigned to PIF
X
[1]
These parameters are not available on 125–500 hp drive controllers.