1—Display Menu
Display parameters can be viewed in any access level. You can scroll
through these parameters with the motor running.
Table 5: 1—Display Menu Parameters
Parameter Code Function Units
Drive. state
Use this
parameter to
monitor drive
controller status.
rdY
rUn
ACC
dEC
CLI
dCb
nSt
Obr
Drive controller status: indicates a fault or the
state of the drive controller:
rdY = drive controller is ready
rUn = motor in steady state
ACC = accelerating
dEC = decelerating
CLI = in current limit
dCb = DC injection braking
nSt = commanded to freewheel stop
Obr = braking with deceleration ramp
adaptation
—
Freq. Ref. - Hz FrH Reference frequency Hz
Output Freq. -
Hz
rFr Output frequency applied to the motor Hz
Motor Speed -
RPM
SPd
Motor speed estimated by the drive controller.
Based on nominal motor speed (nSP) entry.
See Table 11 on page 43.
RPM
Motor Current -
A
LCr Motor current A
NOTE: If USP is
greater than 9999,
the display value
is USP/1000.
Machine Spd. USp
Machine speed estimated by the drive
controller. USP is proportional to rFr scaled by
the coefficient, USC, which is adjustable in the
2—Adjust menu. If USP becomes greater than
9999, the display is divided by 1000.
—
Output Power - % Opr
Output power estimated by the drive controller.
100% corresponds to nominal power.
%
Mains Voltage V ULn Mains voltage V
Motor Thermal -
%
tHr
Thermal state: 100% corresponds to the
nominal motor thermal state. Above 118%, the
controller trips on OLF (motor overload fault).
%
Drive Thermal -
%
tHd
Thermal state of the drive controller: 100%
corresponds to the nominal drive controller
thermal state. Above 118%, the controller trips
on OHF (drive overheating fault). It resets when
the thermal state goes below 70%.
%
Last Fault LFt Displays the last fault. —
Consumption APH Energy consumed
kWh or
MWh