VVDED397047USR6/03 Chapter 2—Menus
06/2003 3—Drive Menu
43
Table 11: 3—Drive Menu Parameters
Parameter Code Description
Adjustment
Range
Factory
Setting
Nom.Mot.Volt- V UnS
Motor nameplate nominal
voltage.
ATV58••••M2
ATV58••••N4
200 to 240 V
200 to 500 V
230 V or
400/460 V
[1]
Nom.Mot.Freq
- Hz
FrS
Motor nameplate nominal
frequency.
10 to tFr
50/60 Hz
[1]
The FrS setting defines the frequency at which nominal
motor voltage (UnS) is applied to the motor. FrS cannot be
set above the maximum output frequency setting tFr.
NomMotCurr.- A nCr
Motor nameplate nominal
current.
0.25 to 1.36
of I
n
[2]
0.9 of I
n
[2]
Nom.MotSpeed
-rpm
nSP
Motor nameplate nominal
speed.
This should be the value that
incorporates slip (i.e. this value
should be the rpm of the motor
when it is fully loaded).
0 to 9999
rpm
depends
on drive
controller
rating
[1]
Depending on the position of the 50/60 Hz switch. Ensure that the switch setting
matches the input frequency (see page 14).
[2]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.
[3]
The factory setting depends on the macro-configuration used: No for Material
Handling, Yes for General Use and Variable torque.
[4]
This parameter is not available on 125–500 hp drive controllers.
[5]
Refer to the drive controller instruction bulletin, VVDED397048US, for duty cycle
ratings of the drive controllers.
These parameters are available only with the I/O extension card installed.
Menu
3
FrS
60 120
460
UnS
Voltage profile
when FrS = 60 Hz
Voltage profile
when FrS = 120 Hz