Inverter/Charger Installation
2–46 975-0239-01-01
This manual for use by qualified personnel only
3. Connect L1 and L2, AC wiring from each INV Grid breaker to the
corresponding AC Input (AC1) terminal on each of the three inverters.
4. If the installation includes a second AC source, connect L1 and L2 AC wiring
from each INV Gen breaker to the corresponding AC Input (AC2) terminal on
each of the three inverters.
5. Connect L1 and L2, AC wiring from each INV AC Load terminal from each of
the three inverters, to the corresponding AC INV Out breaker terminal in the
Xantrex XW PDP.
6. Connect L1 and L2, AC Load wiring to the INV Out (AC Load) power
distribution bar.
7. If the installation includes a second AC source, connect L1 and L2 AC wiring
from the Generator (or other source) disconnect to the Gen breaker power
distribution bars.
8. Connect L1 and L2, AC wiring from the Utility Grid distribution panel to the
Grid breaker power distribution bars.
9. Connect neutral wiring from INV1 (supplied with Xantrex XW PDP), INV2
(supplied in 865-1050) and INV3 (custom, see material list) to the neutral
distribution bar in the Xantrex XW PDP.
10. Connect ground wiring from INV1 (supplied with Xantrex XW PDP), INV2
(supplied in 865-and INV3 (user supplied for single AC source and included
in 865-1050 for Dual AC source) to the ground distribution bar in the
Xantrex XW PDP.
Figure 2-32 Triple-Inverter AC Breaker Arrangement and Wiring Enlargement with Dual AC Input Sources
Power Distribution bars in the Xantrex
XW Power Distribution Panel accept
up to a #2/0 AWG cable (maximum).
See Figure 2-9 on page 2–14
for torque requirements.