Mounting
975-0239-01-01 4–3
This manual for use by qualified personnel only
MPPT Voltage Range
The Xantrex XW SCC maximum power point tracking algorithm maximizes the
output energy of PV arrays as long as the operating voltage is within the MPPT
operational window. Ensure that the PV array used in the system operates within
the MPPT operational window.
Effects of array voltages outside of the MPPT operational window are shown in
Table 4-1.
Mounting
The instructions in this section apply to an installation including the power
distribution panel. Installation procedures will vary according to your specific
application. For special applications, consult a qualified electrician or a certified
Schneider Electric dealer.
Table 4-1 MPPT Operational Window
Voltage Effect of Array Voltage
Xantrex XW
Series Mode
V
oc
< V
batt
(system battery voltage)
Xantrex XW SCC not operating. Low Light
V
MPP
< V
batt
Harvest of solar energy less
than optimal.
Charging
V
MPP
= V
batt
to 120 Vdc Maximum harvest of solar
energy.
Charging
(MPPT window)
120 Vdc < V
MPP
< 140 Vdc Xantrex XW SCC reduces the
output current limit to protect
the unit from voltage spikes.
Input voltage
derating
V
MPP
> 140 Vdc
(or V
oc
> 140 Vdc)
Xantrex XW SCC shuts down.
Unit may be damaged if
V
oc
>150V.
Over-voltage
fault
Important: Installations must be compliant with all local electrical codes.
Installation of this equipment should only be performed by a qualified electrician
or by a Certified Renewable Energy (RE) System installer.