Xantrex XW System Accessories Installation
5–6 975-0239-01-01
This manual for use by qualified personnel only
6. Place the unit into the mounting plate and secure it with four #6 screws.
7. Peel off the protective plastic coating covering the screen and indicator light.
To flush mount the Xantrex XW System Control Panel with no mounting plate:
1. Peel the backing from the supplied mounting template sticker and place it in
your chosen installation location. Use the template to mark the location for
the area to be cut out.
2. Pilot-drill the mounting holes (if necessary, depending on your mounting
surface) and, using a jigsaw, cut out the hole in which the Xantrex XW
System Control Panel will be inserted.
3. Route the network cable(s) from other Xantrex Xanbus-enabled devices
inside the wall and through the opening.
4. Connect the network cable(s) (and terminator if necessary) to either input on
the back of the Xantrex XW System Control Panel. See Figure 5-4.
Connect a network terminator to the Xantrex XW System Control Panel if it is
the last device at the end of a series-type network layout.
5. Place the unit in the opening and secure it with four #6 screws.
6. Peel off the protective plastic coating covering the screen and indicator light.
Figure 5-5 Securing the Xantrex XW System Control Panel
:
CAUTION: Equipment damage
Connect the Xantrex XW System Control Panel only to other Xantrex
Xanbus-enabled devices.
Although the cabling and connectors used in this network system are the same
as Ethernet connectors, this network is not an Ethernet system. Equipment
damage may result from attempting to connect these two different systems.