Grounding
975-0239-01-01 4–9
This manual for use by qualified personnel only
Grounding
The Xantrex XW SCC can be configured to be compatible with either
negative-grounded or ungrounded PV systems.
The maximum size of the ground conductor is #6 AWG (16 mm
2
). This wire
gauge is determined by electrical code requirements regarding conduit
knockout sizes, wire bending radius, and space available within the Xantrex XW
Series wiring compartment. For ground conductor requirements for your specific
installation, consult your local electrical code.
Internal Ground Fault Protection
The Xantrex XW SCC has a PV ground fault protection (Xantrex PV GFP) fuse
(600 V, 1 A) and a PV negative-ground jumper located inside the wiring
compartment. These provide a negative ground bond and ground-fault
protection for negative grounded PV array systems common in North American
installations. Replace the fuse with Littelfuse KLKD 1 or equivalent.
WARNING: Fire hazard
Fuses must only be replaced by qualified service personnel, such as a
certified electrician or technician. For continued protection against risk of fire,
replace only with the same type and rating of fuse.
If Xantrex PV GFP is enabled, do not ground either PV negative or battery
negative circuits. Grounding these circuits will defeat the internal Xantrex PV
GFP protective function.
WARNING: Shock hazard
Disconnect PV and battery circuits before removing the grounding connections
or before removing or installing the Xantrex PV GFP fuse. Wait at least 4 minutes
for the internal circuitry to discharge before servicing the unit.
Important: Only one Xantrex XW SCC is to have the Xantrex PV GFP fuse
installed in installations with multiple parallel units. Before mounting and
connecting the Xantrex XW Solar Charge Controllers, remove the Xantrex PV GFP
fuse from each unit except one.
CAUTION
The factory default configuration of the Xantrex XW SCC will ground the PV array
negative to the chassis ground through the internal Xantrex PV GFP fuse.
The Xantrex PV GFP circuit must be disabled for ungrounded PV arrays.