Seitenansicht 128
The Xantrex XW Automatic Generator Start
975-0239-01-01 5–15
This manual for use by qualified personnel only
Connecting the Generator
To connect the Xantrex XW Automatic Generator Start to a generator, you must
identify the start wiring configuration of the generator you want to use.
Generators must be auto-start capable, and generators equipped with remote
operation connections are ideal.
If the generator is equipped for remote operation, you must examine the wiring of
the remote cable and connector (or read your generator’s documentation,
if available) and identify the following wires:
•Ground
•Start
•Stop
Generator run signal, also known as the Hour Meter or Switched B+
(battery positive)
Wiring
requirements
To wire the Xantrex XW Automatic Generator Start to the generator, you need #16
or #18 AWG wire connected between contacts 12 to 20 on the wiring harness.
How many of these wires you connect and in which combination depends on
your generator type.
Generator types The Xantrex XW Automatic Generator Start has 13 preset generator
configurations, or “Gen Types” (see the Xantrex XW Automatic Start Owner’s
Guide for details on Generator Types). To ensure that the Xantrex XW Automatic
Generator Start is compatible with your generator’s starting circuitry, you must
select your type of generator from the Xantrex XW Automatic Generator Start
menu on the Xantrex XW System Control Panel after completing the installation.
This section describes the generator configurations and provides diagrams for
connecting the wiring harness to the generator’s start wiring.
Important: You can only change GenType after you have put the system or the
Xantrex XW Automatic Generator Start into Standby mode. See the Xantrex XW
Inverter/Charger Operation Guide for instructions on putting the system in
Standby Mode.
Important: For an explanation of the terminology used in the following section,
refer to Appendix B of the Xantrex XW Automatic Generator Start Owner’s
Guide. For more information about Xantrex XW Automatic Generator Start
internal relay activity and timing, see the Xantrex XW Automatic Generator Start
Owner’s Guide.