Commissioning
975-0239-01-01 4–19
This manual for use by qualified personnel only
Commissioning
During commissioning, the Xantrex XW Solar Charge Controller prompts the
installer to enter important system information such as the nominal battery
voltage, battery type, and battery bank capacity. Ensure the system information
is available prior to commissioning.
If a Xantrex XW System Control Panel is present, the Xantrex XW System Control
Panel is intended to be the configuration interface, so the prompt screens are
suppressed. If you prefer to configure using the prompt screens, disconnect the
Xantrex Xanbus cable connecting the Xantrex XW System Control Panel from the
Xantrex XW SCC before powering up for the first time.
Configuration Screens
When power is first applied to the Xantrex XW SCC, several configuration
screens prompt you to enter the following information:
A “DC out” (battery) connection, which enables the Xantrex XW SCC to read
and share the same battery information with other Xantrex Xanbus-enabled
devices that charge or invert from the same battery bank.
Battery type: Flooded (default), Gel, AGM, Custom.
If you select Custom, the settings for battery type match the default settings
for Flooded batteries until you reconfigure the settings on the Custom Battery
menu.
Nominal battery voltage of the battery bank connected to the Xantrex XW SCC.
The Xantrex XW Solar Charge Controller automatically detects battery
voltages of 12 V, 24 V and 48 V.
Battery bank capacity, in amp-hours.