Step 4: Wiring the Inverter
975-0239-01-01 2–23
This manual for use by qualified personnel only
Grounding the AC System
See Table 2-4 on page 13 for torque values for the AC terminal and AC Ground
bar. See Figure 2-8 on page 2–13 for torque requirements for the ground bar in
the Xantrex XW Power Distribution Panel.
Important: Place the neutral-to-ground bond in a permanently installed AC
distribution panel that is part of the system. This may be a main panel or a
sub-panel.
Figure 2-16 Grounding the AC System using the Distribution Panel
Actual ground requirements may vary.
* Depending on the location of the generator and local
code requirements, the generator disconnect may be
located in the power distribution panel.
In an off-grid installation (i.e., where no utility grid is
available), the generator can be connected to the
breakers provided in the Xantrex XW Power Distribution
Panel. No additional breaker is required.
*This Grounding Conductor may not be required if the DC ground is used instead.
Only one ground bond from the Xantrex XWPDP to the main panel needs to be in place.