Electrical Specifications
975-0540-01-01 Revision B A–3
This guide is for use by qualified personnel only.
MPPT Voltage Range
The charge controllers Maximum Power Point Tracking (MPPT) algorithm
maximizes the output energy of PV arrays as long as the operating voltage is
within the MPPT operational window. Make sure that the PV arrays used in the
system operate within the MPPT operational window. The operational window is
shown below.
Operating Below the PV Array Voltage Full Power Range
When the charge controller is operating on a 48 V battery bank and a PV array
where the MPP is below 230 V, full output power is not assured. Figure A-2 and
Figure A-3 show the maximum output current and maximum output power that
can be produced when the charge controller is operating below 230 V. The
actual amount of current and power that your charge controller can produce
below 230 V will depend on the actual battery voltage and the amount of solar
power available from your panels. Full output current is available on 24 V battery
systems across the entire input voltage operating range.
NOTICE
PV array voltages often exceed STC voltage specifications, especially
when the array is cold. A voltage temperature correction factor based on
the local code (i.e., NEC 690 or CEC Section 50), ambient temperature
conditions, and module manufacturer specifications must be applied to the
array STC V
OC
to keep array voltage within specifications listed above.
PV array current might exceed STC current specifications, especially under
intense sunlight, certain atmospheric conditions, or from reflections (i.e,
water, snow, or ice). Local codes typically apply a multiplier to the PV array
I
sc
to determine “maximum current” for design purposes. The “Absolute
Maximum Array Short Circuit Current” specification above includes the
125% multiplier required by the NEC and the CEC. Accordingly, the PV
array STC I
sc
cannot exceed 28 A.
Figure A-1 MPPT operational window
Note:
Max V
OC
600 V
Input current limit 35 A (array
I
sc
including 125% code multiplier)
Output current limit 80 A