Installation
2–12 975-0540-01-01 Revision B
This guide is for use by qualified personnel only.
Connecting the Unit
The following procedure is illustrated in Figure 2-9 on page 2–13.
To connect the charge controller in a negative-grounded system:
1. Make sure the PV array disconnect and battery disconnect are turned off.
2. Install a cable clamp into each knockout being used.
3. Ground the charge controller: connect a grounding conductor between a
charge controller ground lug and the grounding electrode (as shown in
Figure 2-9 on page 2–13).
4. Connect the PV array’s negative (–) output to the charge controller terminal
marked
PV –.
5. Connect the PV array’s positive (+) output to the PV array disconnect.
6. Route another positive (+) cable from the other end of the PV array
disconnect to the charge controller terminal marked
PV +.
7. Connect the negative () battery cable to the charge controller terminal
marked
BAT –.
8. Connect a positive (+) cable from the charge controller terminal marked
BAT + to the battery disconnect.
9. Connect a second positive (+) cable to the other side of the battery
disconnect and connect to the positive (+) battery terminal.
10. Torque the charge controller’s battery terminals to 25 lbf.in (2.8 Nm) and the
PV terminals to 15 lbf.in (1.7 Nm). Allow some slack on the cables within the
charge controller and secure the wiring with strain reliefs or cable clamps.
DANGER
HAZARD OF ELECTRIC SHOCK
Whenever a PV array is exposed to light, a shock hazard exists at the output
wires or exposed terminals. Open the array disconnect switch before making
the connections.
Failure to follow these instructions will result in death or serious injury.
CAUTION
REVERSE POLARITY DAMAGE
Before energizing the charge controller from either the PV array or from the
battery, check the polarity of all power connections. Positive (+) must be
connected to positive (+). Negative (–) must be connected to negative (–).
Failure to follow these instructions can result in equipment damage.