Seitenansicht 27
Installation
2–10 975-0540-01-01 Revision B
This guide is for use by qualified personnel only.
A label providing details on each connector and torque requirements for each
terminal is affixed to the inside of the wiring compartment cover plate.
Wire Size and Over-current Protection Requirements
PV Current Rating
The maximum PV array input current specification is 28 A I
sc
at STC. The gauge
of PV wiring must coordinate with local electrical code requirements and the total
array short circuit current, based on the published I
SC
rating of the PV panels
installed in the system.
Minimum Wire Gauge
For installations where the PV array is specified at the 35 A maximum, the
recommended smallest wire size is #8 AWG (10 mm
2
)
1
copper wire with a 75 °C
(167 °F) insulation rating. The wire gauge requirements vary with those of the
local jurisdiction. For details, consult the electrical code.
Figure 2-8 DC terminal connector locations
BATTERY
+
_
NEG. GND PV.
PV- PV+
POS. GND PV.
XANBUSXANBUS BTS AUX
TERMINALTORQUE
25 lbf.in (2.8 N m) 15 lbf.in ( 1.7 Nm)
TERMINAL TORQUE
COM
NO
NC
WARNING
HAZARD OF ELECTRIC SHOCK, ENERGY, AND FIRE
The wiring, over-current protection devices (fuses and circuit breakers), and
installation methods used must conform to all national and local electrical
code requirements. Wiring must be protected from physical damage with
appropriate methods such as the use of conduit and strain relief clamps.
To prevent intermingling with hazardous voltage-level wiring, the BTS, auxiliary
output, and network cables must pass through a different conduit than the PV
and battery cables.
Failure to follow these instructions can result in death or serious injury.
1.Based on NEC Table 310-16.