Installation
2–16 975-0540-01-01 Revision B
This guide is for use by qualified personnel only.
Auxiliary Output Connections
The auxiliary output (dry relay contacts) provides a connector which can accept
wire sized from #22 to #14 AWG (0.5 to 2.5 mm
2
), copper solid or stranded. As
shown in Figure 2-11, the auxiliary output can control 12 VDC power to a fan to
vent the battery compartment. For this application, the charge controller’s
auxiliary output must be configured to activate when the batteries reach a pre-set
voltage level. See “Configuring the Auxiliary Output” in the operation guide.
HAZARD OF ELECTRIC SHOCK AND FIRE
The auxiliary NO and NC dry contacts are rated up to 60 VDC and up to 8 A.
Do not expose the auxiliary contacts to voltages or currents higher than this
rating. Provide external over-current protection rated at 8 A maximum.
Failure to follow these instructions can result in death or serious injury.
Figure 2-11 Auxiliary output vent fan application
-
+
BATTERY
+
_
NEG. GND PV.
PV- PV+
POS. GND PV.
XANBUSXANBUS BTS AUX
TERMINAL TORQUE
25 lbf.in (2.8 Nm) 15 lbf.in (1.7 Nm)
TERMINAL TORQUE
In order from left:
NC
NO
COMMON