Installation
2–14 975-0540-01-01 Revision B
This guide is for use by qualified personnel only.
To connect the charge controller in a positive-grounded or floating system:
Follow the same steps as above for a negative-grounded charge controller,
except note the location of the PV array disconnect switch will vary as
follows:
For positive-grounded systems, the PV array disconnect switch must be
in the negative conductor.
For floating systems, the PV array disconnect switch must be a 2-pole
type connected in both the positive and negative conductors as per local
electrical code in the United States and Canada.
In general, the same rules apply for disconnect switches as for battery circuits:
they must be located in all ungrounded conductors. Requirements vary so
consult local code.
Connecting Multiple PV Array Strings to One Unit
The charge controller has two three-pole connectors, allowing up to three PV
array strings to be combined in the charge controller. Input connectors can
accept #6 to #14 AWG (13.5 to 2.5 mm
2
) solid or stranded wire.
WARNING
HAZARD OF FIRE
Fuses are required when paralleling (combining) more than two PV strings.
Fuses must be installed in a combiner or in a PV array disconnect switch.
These items are not provided with the charge controller.
Failure to follow these instructions can result in death or serious injury.