Default Battery Charger Settings
975-0540-01-01 Revision B A–5
This guide is for use by qualified personnel only.
Default Battery Charger Settings
All settings in the following table are based on a 48 V nominal battery bank. For a
24 V nominal battery bank, divide the voltage values in this table by two.
Mechanical Specifications
Setting
Battery Type
Flooded
a
a.When Custom is selected for the battery type, the default settings are
based on the flooded battery type.
Gel AGM
Equalize Voltage 64.0 V n/a n/a
ReCharge Voltage 50.0 V 50.0 V 50.0 V
Bulk Voltage 57.6 V 56.8 V 57.2 V
Absorption Voltage 57.6 V 56.8 V 57.2 V
Float Voltage 54.0 V 55.2 V 53.6 V
Absorption Time 360 min 360 min 360 min
Batt Temp Comp -108 mV/C -108 mV/C -84 mV/C
Enclosure Type IP20, indoor, ventilated, aluminum sheet metal chassis with 7/8" and
1" (22.22 mm and 27.76 mm) knockouts and aluminum heat sink
Maximum and Minimum Wire Size
in Conduit
#6 AWG to #14 AWG (13.5 to 2.5 mm
2
)
Maximum and Minimum Wire Size
Rating of PV Terminal Block
#6 AWG to #14 AWG (13.5 to 2.5 mm
2
)
Maximum and Minimum Wire Size
Rating of Battery Terminal Block
#2 AWG to #14 AWG (35 to 2.5 mm
2
)
Wire Size Rating of Auxiliary
Output Connector
#16 AWG (1.5 mm
2
)
Operating Temperature Range
(derate above 45 °C)
-4 to 149 °F (-20 to +65 °C)
(output power to be derated linearly to zero at 65 °C)
Storage Temperature -40 to 185 °F (-40 to +85 °C)
Altitude Limit (operating) Sea level to 6,500 feet (approximately 2000 m)
Dimensions (H × W × D) 30 × 8 5/8 × 8 5/8" (760 × 220 × 220 mm)
Mounting Vertical wall mount
Weight (charge controller only) 29.8 lb (13.5 kg)
Weight (shipping) 38.3 lb (17.4 kg)