Wiring
975-0540-01-01 Revision B 2–13
This guide is for use by qualified personnel only.
Figure 2-9 Typical wiring diagram for a negative-grounded system (48 V battery bank shown)
LEGEND
Ground
DC Positive
DC Negative
CHASSIS
GROUND
PV -
BAT
PV +
Grounding and disconnect locations will vary according to system design and local electrical codes.
Disconnect
(configuration will vary)
48 V battery bank
To inverter
The positive or negative of the
battery can be grounded
independent of the array grounding.
4800 W STC array
(2 x 2400 W strings)
Ground
For negative-grounded
PV array, install fuse here.
100 A
DC
(typical)
For positive-grounded PV
array, install fuse here.