Charge Controller Troubleshooting
975-0540-01-01 Revision B 3–3
This guide is for use by qualified personnel only.
The charge
controller’s Error/
Warning (red) LED is
on or flashing.
An active fault, error, or warning is
present on the charge controller.
See “Viewing Active Faults, Errors,
and Warnings” in the Xantrex XW
MPPT 80 600 Solar Charge Controller
Operation Guide to determine which
alarm is active on the charge
controller. The tables in this section
provide detailed information on why
various alarms could be occuring on
the charge controller.
The charge
controller’s Error/
Warning (red) LED is
on, and the SCP
indicates a ground
fault (F56) for the
charge controller.
A ground fault has caused the ground
fault protection fuse to blow, or a
normally ungrounded array contains a
ground fault.
See “Replacing the Ground Fault
Protection Fuse” on page 3–4 or
“Ground Faults in a Normally
Ungrounded Array” on page 3–5.
The charge
controller’s Error/
Warning (red) LED is
on, and the SCP
indicates an output
under voltage error
(F11) for the charge
controller.
A. The default configuration for the
charge controller is a 48 V battery
bank, and you have installed the
charge controller on a 24 V battery
bank.
B. The batteries are dead or
undercharged.
A. Use the SCP to configure the
charge controller for 24 V operation.
See “Configuring Battery
Characteristics and Battery Charging”
in the Xantrex XW MPPT 80 600 Solar
Charge Controller Operation Guide for
more information.
B. Check the battery voltage to see if
the batteries are within operating
specifications. If necessary, replace
them with new batteries, or use a
device capable of performing dead
battery charging.
The charge controller
does not show up on
the SCP or it drops off
the network
periodically.
A. Network terminators have not been
installed at both ends of the Xanbus
network.
B. The total network length exceeds
the maximum length specification.
A. Install a terminator at each far end
of the network. See “Network
Components” on page 2–17 for more
information.
B. See “Network Layout” on
page 2–18 for specifications.
The charge controller
does not produce any
power.
A. No PV input voltage.
B. PV input voltage is not within
operating range.
A. Change the PV disconnect switch
from the off position to the on position.
B. Make sure that the PV panels are
configured to provide voltages within
the charge controller’s operating
voltage window.
Table 3-1 Charge controller problems
Problem Possible Cause Solution