Planning Instruction 66571758GB0 49/2011 Fire Detection
FX 3NET + SLC FIRE ALARM SYSTEM
Part 1: General Rules
These are the planning instructions for an FX 3NET fire detection and alarm system
consisting of
- FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET control panels
- SLC compatible intelligent field devices
In this document FX refers to all FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET panels. For
information specifically related to a specific panel model, that model type is indicated.
We reserve the right to make technical changes without notice.
The planning instructions consist of 3 parts:
- Part 1: General Rules 6657 1758GBx
- Part 2: System Devices 6657 1759GBx
- Part 3: Additional Information 6657 1760GBx
See also the following instructions:
- User guide of the WinFX3Net Configuration Tool 6657 1782GBx
- FX3Net Configuration Data 6657 1783GBx
- FX3Net System Capacity Calculation Tool 6657 1746GBx
Note!
Instructions given by local authorities must be followed when planning the system.
Seitenansicht 0
1 2 3 4 5 6 ... 63 64

Inhaltsverzeichnis

Seite 1 - Part 1: General Rules

Planning Instruction 66571758GB0 49/2011 Fire Detection FX 3NET + SLC FIRE ALARM SYSTEM Part 1: General Rules T

Seite 2

Planning Instruction 66571758GB0 Fire Detection 10 3. FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET construction The FX panel is a modular construct

Seite 3

Planning Instruction 66571758GB0 Fire Detection 11 3.2 FXL 3NET cabinet The FXL cabinet has space for the following - 1 x UI2 - 1 x MC2 - 1

Seite 4 - End user

Planning Instruction 66571758GB0 Fire Detection 12 3.5 FX battery cabinet The FX battery cabinet has space for the following - 4 x battery 12

Seite 5

Planning Instruction 66571758GB0 Fire Detection 13 4. Mechanical installation 4.1 Installation, FX 3NET and FXL 3NET control panels Schneider

Seite 6

Planning Instruction 66571758GB0 Fire Detection 14 4.2 Installation, FXM 3NET control panel Schneider Electric Pelco Finland Oy Kalkkipellon

Seite 7

Planning Instruction 66571758GB0 Fire Detection 15 4.3 Installation, FXS 3NET control panel Schneider Electric Pelco Finland Oy Kalkkipellon

Seite 8 - DAPXFMPX REPX

Planning Instruction 66571758GB0 Fire Detection 16 5. FX 3NET, multi-panel networked system FX 3NET is the solution for fire detection systems

Seite 9

Planning Instruction 66571758GB0 Fire Detection 17 Example 2 Consider an industrial site with two large buildings and a gate building. The gate s

Seite 10 - MC2 OP

Planning Instruction 66571758GB0 Fire Detection 18 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Seite 11

Planning Instruction 66571758GB0 Fire Detection 19 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Seite 12

Planning Instruction 66571758GB0 Fire Detection 2 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 13

Planning Instruction 66571758GB0 Fire Detection 20 6. Addressable detection circuits, addresses, zones 6.1 FX-SLC addressable detection circui

Seite 14

Planning Instruction 66571758GB0 Fire Detection 21 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Seite 15

Planning Instruction 66571758GB0 Fire Detection 22 Closed detection circuit (highly recommended) A closed detection circuit gives the highest saf

Seite 16 - Panel 1 Panel 2 Panel 3

Planning Instruction 66571758GB0 Fire Detection 23 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Seite 17

Planning Instruction 66571758GB0 Fire Detection 24 6.4.1 Control groups for all event types (Ctrl A and Ctrl B) Control group A and B inputs a

Seite 18

Planning Instruction 66571758GB0 Fire Detection 25 Sequence example 2: reset during delay Input (e.g. MCP in alarm state)Fire alarm deviceFire a

Seite 19

Planning Instruction 66571758GB0 Fire Detection 26 6.4.4 Control group use for delayed alarm Control groups A and B can be used together with

Seite 20

Planning Instruction 66571758GB0 Fire Detection 27 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Seite 21

Planning Instruction 66571758GB0 Fire Detection 28 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Seite 22

Planning Instruction 66571758GB0 Fire Detection 29 EOL resistor, Exi 4k7, 5%, not Exi 2k94, 1%, not Exi 4k7, 5%, Exi 2k94, 1%, Exi Max cable

Seite 23

Planning Instruction 66571758GB0 Fire Detection 3 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 24

Planning Instruction 66571758GB0 Fire Detection 30 8. Cabling 8.1 Cables of addressable detection circuit x10x10x10C CC1472058369147205836914

Seite 25

Planning Instruction 66571758GB0 Fire Detection 31 8.2 Cables of conventional detection circuits CLC, alarm device lines, input/output lines

Seite 26 - Fire detection

Planning Instruction 66571758GB0 Fire Detection 32 8.3 Cables of serial communication lines and power supply FXSFMPXDAPXREPXMCOXFX_12181818181

Seite 27

Planning Instruction 66571758GB0 Fire Detection 33 8.4 Grounding of communication cables FX y serial adapterFX x serial adapterGND TR- TR+SYS

Seite 28

Planning Instruction 66571758GB0 Fire Detection 34 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Seite 29

Planning Instruction 66571758GB0 Fire Detection 35 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +

Seite 30

Planning Instruction 66571759GB0 49/2012 Fire Detection FX 3NET + SLC FIRE ALARM SYSTEM Part 2: System Devices

Seite 31

Planning Instruction 66571759GB0 Fire Detection 2 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 32

Planning Instruction 66571759GB0 Fire Detection 3 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 33

Planning Instruction 66571759GB0 Fire Detection 4 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 34

Planning Instruction 66571758GB0 Fire Detection 4 1.3 Regulations EN54-14 “Guidelines for Planning, Installation, Commissioning and Maintenance

Seite 35

Planning Instruction 66571759GB0 Fire Detection 5 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 36 - Part 2: System Devices

Planning Instruction 66571759GB0 Fire Detection 6 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 37

Planning Instruction 66571759GB0 Fire Detection 7 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 38

Planning Instruction 66571759GB0 Fire Detection 8 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 39

Planning Instruction 66571760GB0 49/2011 Fire Detection FX 3NET + SLC FIRE ALARM SYSTEM Part 3: Additional Information

Seite 40

Planning Instruction 66571760GB0 Fire Detection 2 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 41

Planning Instruction 66571760GB0 Fire Detection 3 1. Examples of FX 3NET system structure 1.1 System structure examples Example 1 S1S1S1 S1

Seite 42

Planning Instruction 66571760GB0 Fire Detection 4 Example 3: FX 3NET communication segments, long distances CCCCCCCCCCCCMMMMMMMMMMMMFX_FX_FX_FX_

Seite 43

Planning Instruction 66571760GB0 Fire Detection 5 Example 4: Factory area  FX_FX_FX_ FX_FX _FX_ FX_FX_S1S1S1S1S1S1S2S2S2MLMLMLMLMLMLMLMLMLMLS2S

Seite 44

Planning Instruction 66571760GB0 Fire Detection 6 1.2 Cable length of a segment FX_ FX_FX_Max. 1000 m abcFX_FX_FX_FX_a + b+ c = maks. 1000

Seite 45

Planning Instruction 66571758GB0 Fire Detection 5 1.4 Example of a site plan for the FX 3NET fire detection system 008016015001 002 003 004 005

Seite 46

Planning Instruction 66571760GB0 Fire Detection 7 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 47 - Max. 5 km *)

Planning Instruction 66571760GB0 Fire Detection 8 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 48

Planning Instruction 66571760GB0 Fire Detection 9 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 49 - Max. 1000 m

Planning Instruction 66571760GB0 Fire Detection 10 4. FX 3NET, FXL 3NET, FXM 3NET and FXS 3NET connections, settings and fuses 4.1 FX 3NET and

Seite 50

Planning Instruction 66571760GB0 Fire Detection 11 4.2 FXM 3NET panel external connections Schneider Electric Pelco Finland Oy Kalkkipellon

Seite 51

Planning Instruction 66571760GB0 Fire Detection 12 4.3 FXS 3NET panel external connections Schneider Electric Pelco Finland Oy Kalkkipellon

Seite 52

Planning Instruction 66571760GB0 Fire Detection 13 4.4 Connectors on the MC2 board Terminal name Connector symbol Purpose Description 24 V -

Seite 53

Planning Instruction 66571760GB0 Fire Detection 14 4.5 Connectors on the PS board Terminal name Connector symbol Purpose Description 30 VAC

Seite 54

Planning Instruction 66571760GB0 Fire Detection 15 4.7 Connectors on each CLC board Terminal name Connector symbol Purpose Description - Conve

Seite 55

Planning Instruction 66571760GB0 Fire Detection 16 4.9 Connectors on each IOC board Terminal name Connector symbol Purpose Description Alarm

Seite 56

Planning Instruction 66571758GB0 Fire Detection 6 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 57

Planning Instruction 66571760GB0 Fire Detection 17 4.10 FX 3NET, FXL 3NET and FXM 3NET Fuses The 30VAC input from the transformer is protected

Seite 58

Planning Instruction 66571760GB0 Fire Detection 18 4.11 FX 3NET, FXL 3NET and FXM 3NET Battery backup The FXM cabinet has space for 2 x 12 Ah /

Seite 59

Planning Instruction 66571760GB0 Fire Detection 19 5. FX Settings and configuration 5.1 Settings in the FX panel Settings on the FX-MC2 board

Seite 60

Planning Instruction 66571760GB0 Fire Detection 20 Settings on the FX-CLC board With settings on the FX-CLC board, the following can be set and

Seite 61

Planning Instruction 66571760GB0 Fire Detection 21 Settings on the FX-IOC board With settings on the FX-IOC board, the following can be set and

Seite 62

Planning Instruction 66571758GB0 Fire Detection 7 Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +3

Seite 63 - + 16

Planning Instruction 66571758GB0 Fire Detection 8 2.5 FX 3NET stand-alone system diagram Schneider Electric Pelco Finland Oy Kalkkipellont

Seite 64

Planning Instruction 66571758GB0 Fire Detection 9 2.6 Networked FX 3NET system diagram Schneider Electric Pelco Finland Oy Kalkkipellontie 6