Functions (continued)
Altivar
®
12
variable speed drives
Underload detection
See page 34.
Overload detection
See page 34.
Sleep/Wake-up
Allowsthevariablepumptocometoacompletestopwhentheowrateis
consideredtoolow,belowanadjustable“sleepthreshold”(LSP+SLE)andtime
delay (tLS).
When the system is in “sleep” state, if the PID feedback value (showing the pressure
downstream of the pump) falls below a “wake up” threshold (UPP), the variable
pump is restarted.
PID
feedback
Motor
frequency
Sleep
Wake-up
Sleep/Wake-up functions
LSP: Low speed
SLE: Sleep threshold offset
UPP: Wake-up threshold
tLS: Sleep threshold operating time
PID feedback supervision
Once the variable pump is running at maximum speed and at the same time the PID
feedback is lower than the supervision threshold (LPI) at the end of a time delay
(tPI), the drive switches to fallback mode. There are two possible scenarios (see
graphs below):
v Thedriveperformsafreewheelstopanddisplaysaspecicfaultcode1.
v Congurablexedspeedoperationwithdisplayofaspecicfaultcode2.
The drive reverts to regulation mode when the PID feedback returns to the
supervision threshold (LPI).
t
HSP
FPI
< tPI tPI
HSP - AP0
LPI
t
LPI + 3 %
LPI - 2 %
1
2
PID feedback supervision
PID
feedback
Motor
frequency
LPI: PID feedback supervision threshold
HSP: High speed
FPI: Fallback speed
APO: Maximum speed detection hysteresis
tPI: PID feedback supervision function time delay
In single variable mode with auxiliary pump, this function is active when both pumps
are operating.
No-load operation detection
Thisfunctionisusedinapplicationswherezeroowcannotbedetectedbythesleep
function alone. It is active when the auxiliary pump is stopped and the variable pump
motorfrequencyreferenceisbelowaconguredthreshold.
It consists of periodically forcing the motor frequency reference to a low value:
v If the request is still present, it results in an increase in the PID error and the drive
reverts to regulation in line with the previous reference.
v Iftherequestisnolongerpresent(zeroow),thePIDerrorwillnotchange,
which is characteristic of no-load operation. The variable pump motor is stopped.
Introduction:
page 8
Specications:
page 10
References:
page 14
Dimensions:
page 18
Connections:
page 22