Functions (continued)
Altivar
®
12
variable speed drives
Ramp time switching
This function is used to switch two acceleration and deceleration ramp times,
which can be set separately.
Enabled by means of 1 assignable logic input.
It is suitable for machines with fast speed correction in steady state and high-speed
lathes with acceleration and deceleration limiting above certain speeds.
Acceleration and deceleration ramp proles
This function can be used to gradually increase the output frequency starting from a
speedreference,followingalinearproleorapresetprole.
v S ramps
The use of S ramps is dedicated to applications involving handling, packaging and
passengertransport;thismethodtakesupmechanicalbacklashandeliminatesjolts,
and also limits “non-following” of speed during rapid transient operation of high-
inertia machines.
v U ramps
The use of U ramps is dedicated to pump applications such as an installation with
centrifugal pump and non-return valve; this method enables valve closing to be
controlled more accurately.
Selecting“linear”,“S”,or“U”proleswillaffectboththeaccelerationand
deceleration ramps.
Automatic adaptation of deceleration ramp
This function is used to increase the deceleration time automatically if the initial
setting is too low when the load inertia is taken into account. It prevents the drive
locking on an “overvoltage on deceleration” fault.
If a braking unit is connected to the drive, this function must be disabled.
Stop types
Thisisusedtodenethedrivestopmode.
There are three stop types:
v Freewheel stop: When the drive is locked, the motor stops in freewheel mode
depending on the application; the motor power supply is cut.
v Stop on deceleration ramp: The motor stops according to the deceleration ramp
timewhichcanbexedoradaptable(seethe“Automaticadaptationofdeceleration
ramp” function).
v Fast stop: Braked stop with an acceptable deceleration ramp time (divided by a
coefcientwhichcanbesetbetween1and10)forthedrive/motorunitwithout
locking in the event of an “overvoltage on deceleration” fault.
Factory-setconguration:Stopon3sdecelerationrampwithautomaticadaptation.
Introduction:
page 8
Specications:
page 10
References:
page 14
Dimensions:
page 18
Connections:
page 22
f (Hz) f (Hz)
HSP
HSP
0 0t t
t2
t1
t2
t1
HSP: High speed
t1=k1xt2(k1:xedroundingcoefcient)
t2: Ramp time set
S ramps
f (Hz)
HSP
0
t2
t1
f (Hz)
HSP
t1
0
t2
t t
HSP: High speed
t1=k2xt2(k2:xedroundingcoefcient)
t2: Ramp time set
U ramps
t
1 Fast stop
2 Stop on deceleration ramp
3 Freewheel stop
123
f (Hz)
Stop types