Functions (continued)
Altivar
®
12
variable speed drives
2
nd
current limit
A 2
nd
currentlimitcanbeconguredbetween0.25and1.5timesthenominaldrive
current and can be used to limit the torque and the rise in motor temperature.
Switching between the two current limits is enabled via a logic input or via the
Modbus serial link.
Automatic DC injection
ThisfunctionenablesstandstillDCinjection,whichcanbesetbetween0and
1.2timesthevalueofthenominaldrivecurrent(factory-setconguration:
0.7 x motor nominal current), as soon as operation is no longer controlled and
the motor speed is zero:
v Either for a period of time, which can be set between 0.1 and 30 s
v Or continuously
Factory-setconguration:FunctionactivewithDCinjectionfor0.5s.
In3-wirecontrol,DCinjectionisonlyactiveiflogicoutputLI1isactive
(assigned to stop).
Motor control proles
Threemotorcontrolprolesareavailabledependingontheapplication
requirements:
v Standard (U/F):Simplemotorcontrolprolemaintainingaconstantvoltage/
frequency ratio with an optional low speed setting.
Prolesuitableforsmallconveyors,applicationswithmotorsconnectedin
parallel, etc.
v Performance (sensorless ux vector control):Prolewhichcanguaranteethe
levelofperformancewithamotorwiththesamepoweroroneratingless.Thisprole
canbeusedtoobtainimproveddynamicspecicationsatlowspeed.
Prolesuitableforrunningmachines,etc.
v Pump/Fan (Kn²): Quadratic ratio for obtaining a torque proportional to the square
ofthespeed.Thisprolecanbeusedtooptimizeenergyconsumptionaccordingto
the load applied to the machine.
Prolesuitableforpumpregulation,airextraction,etc.
Switching frequency, noise reduction
The switching frequency setting between 2 and 16 kHz permits a reduction in the
noise generated by the motor for any application requiring a low level of noise.
The switching frequency can be modulated randomly in order to avoid resonance.
This function can be disabled if it causes instability.
Switching the DC voltage at high frequency is useful for supplying the motor with a
current wave having little harmonic distortion.
This type of operation increases drive overheating.
Factory-setconguration:Lowfrequencysetat4kHz.
Frequency jump
Used to pass a mechanical resonance point likely to cause increased noise or risk of
mechanical breakdown.
Thefrequencyjumpisxed.Itiswithin±1Hzoftheconguredresonancepoint.
Jog mode
Thiscanbeusedforpulseoperationwithminimumramptimes(0.1s),axedspeed
reference set at 5 Hz and minimum time of 0.5 s between 2 pulses.
Enabled by 1 logic input and pulses issued by the operating direction command.
This function is suitable for machines with product insertion in manual mode (for
example, gradual movement of the mechanism during maintenance operations).
Introduction:
page 8
Specications:
page 10
References:
page 14
Dimensions:
page 18
Connections:
page 22
Setting the “DC injection” function with the SoMove
setup software
Energy saving with the
Pump/Fan prole (Kn
2
)
Frequency jump in relation to the resonance point
Reference
f (Hz)