Underload detection
This function stops the motor when it is underloaded. The function is active in
steady state.
Ifthecurrentisbelowanunderloadthresholdforanadjustableperiodoftime,
the drive locks in underload fault mode.
Thecurrentthresholdisadjustablebetween20%and100%ofthenominalmotor
current value.
Hysteresisof10%isappliedtothisthresholdtoconrmtheendofunderload
conditions.Thetimedelayisadjustableupto100s.Whenthisparameterisat0,
the function is deactivated.
This function is particularly suitable for protecting pumps during cavitation.
Overload detection
This function stops the motor when it is overloaded. The function is active in steady
state.
Ifthemotorcurrentishigherthananoverloadthresholdforanadjustableperiodof
time, the drive locks in overload fault mode.
The overload threshold can be set to between 70% and 150% of the nominal motor
current.
Hysteresisof10%isappliedtothisthresholdtoconrmtheendofoverload
conditions.
The time delay can be set at anything up to 100 s. When this parameter is at 0,
the function is deactivated.
Fault acknowledgment
This is used to clear the stored fault and restart the drive if the cause of the fault has
disappeared.
The fault is cleared by a transition of the logic input LI which is assigned to this
function.
Factory-setconguration:Functioninactive.
The restart conditions after a reset are the same as those of a normal power-up.
The following faults can be reset (1): drive thermal overload, motor thermal overload,
line overvoltage, overvoltage on deceleration, overspeed, input phase loss (2), etc.
Parameter protection by condential code
Thisfunctionprotectsthedrivecongurationusinganaccesscode.
Conguration of logic output LO+
Logic output LO+ enables remote signalling of the following information as required:
v Malfunction
v Operation
v Frequency threshold attained
v High speed attained
v Current threshold attained
v Frequency reference attained
v Motor thermal state attained
v 4-20 mA monitoring
v Underload detected
v Overload detected
v Operation of the auxiliary pump with the “Control in single variable mode with
auxiliary pump” function
Conguration of analog output AO1
Analog output AO1 enables remote signalling of the following information as
required:
v Motor current
v Motor frequency
v Ramp output
v PID error
v PID feedback
v PID reference
v Output power
v Motor thermal state
v Drive thermal state
(1) See the complete list of faults in the Altivar
®
12 Programming Manual, available on our
website at “www.schneider-electric.us”.
(2) The “input phase loss” fault is only accessible on drives with a three-phase power supply,
if monitoring of the fault has been enabled (factory-set conguration: enabled).
Introduction:
page 8
Specications:
page 10
References:
page 14
Dimensions:
page 18
Connections:
page 22
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Kommentare zu diesen Handbüchern