Electrical specications (control)
Available internal supplies Protected against short-circuits and overloads:
One 5 V ⎓ supply (± 5%) for the reference potentiometer (2.2 to 10 kW),
maximum data rate 10 mA
One 24 V ⎓ supply (-15%/+20%) for the control inputs, maximum data rate 100 mA
Analog input AI1 1software-congurablevoltageorcurrentanaloginput:
Voltage analog input: 0 to 5 V ⎓ (internal power supply only) or 0 to 10 V ⎓,
impedance 30 kW
Analog current input: X-Y mA by programming X and Y from 0 to 20 mA,
impedance 250 W
Sampling time: < 10 ms
Resolution: 10 bits
Accuracy: ± 1% at 25°C
Linearity: ± 0.3% of the maximum scale value
Factorysetting:Inputconguredasvoltagetype
Analog output AO1 1software-congurablevoltageorcurrentanalogoutput:
Analog voltage output: 0 to 10 V ⎓ , minimum load impedance 470 W
Analog current output: 0 to 20 mA, maximum load impedance 800 W
Update time: < 10 ms
Resolution: 8 bits
Accuracy: ± 1% at 25°C
Relay outputs R1A, R1B, R1C 1 protected relay output, 1 N/O contact and 1 N/C contact with common point
Response time: 30 ms maximum
Minimum switching capacity: 5 mA for 24 V ⎓
Maximum switching capacity:
On resistive load (cos j = 1 and L/R = 0 ms): 3 A at 250 V a or 4 A at 30 V ⎓
On inductive load (cos j = 0.4 and L/R = 7 ms): 2 A at 250 V a or 30 V ⎓
LI logic inputs LI1 to LI4 4 programmable logic inputs, compatible with PLC level 1, standard IEC/EN 61131-2
24 V ⎓ internal power supply or 24 V ⎓ external power supply (min. 18 V, max. 30 V)
Sampling time: < 20 ms
Sampling time tolerance: ± 1 ms
Factory-set with 2-wire control in "transition" mode for machine safety reasons:
LI1: forward
LI2 to LI4: not assigned
Multipleassignmentmakesitpossibletocongureseveralfunctionsononeinput
(for example: LI1 assigned to forward and preset speed 2, LI3 assigned to reverse
and preset speed 3)
Impedance 3.5 kW
Positive logic (Source) Factory setting
State 0 if < 5 V, state 1 if > 11 V
Negative logic (Sink) Software-congurable
State 0 if > 16 V or logic input not wired, state 1 if < 10 V
Logic output LO+, LO- One 24 V ⎓ logic output assignable as positive logic (Source) or negative logic (Sink)
open collector type, compatible with level 1 PLC, standard IEC/EN 61131-2
Maximum voltage: 30 V
Linearity: ± 1%
Maximum current: 10 mA (100 mA with external power supply)
Impedance: 1 kW
Update time: < 20 ms
Maximum I/O wire size and tightening torque 1.5 mm
2
(14 AWG)
0.5 Nm
Acceleration and deceleration ramps Rampprole:
Linear from 0 to 999.9 s
S ramp
U ramp
Automatic adaptation of deceleration ramp time if braking capacities exceeded,
although this adaptation can be disabled (use of braking unit)
Emergency braking ByDCinjection:automaticallyassoonastheestimatedoutputfrequencydropsto
<0.2Hz,periodadjustablefrom0.1to30sorcontinuous,currentadjustablefrom
0 to 1.2 In
Main drive protection features Thermal protection against overheating
Protection against short-circuits between motor phases
Overcurrent protection between motor phases and ground
Protection in the event of line overvoltage and undervoltage
Input phase loss protection, in three-phase
Motor protection Thermal protection integrated in the drive by continuous calculation of the l
2
t
Frequency resolution Display unit: 0.1 Hz
Analog inputs: 10-bit A/D converter
Time constant on a change of setpoint ms 20 ± 1 ms
Introduction:
page 8
References:
page 14
Dimensions:
page 18
Connections:
page 22
Functions:
page 26
Specications (continued)
Altivar
®
12
variable speed drives
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Kommentare zu diesen Handbüchern