Altivar
®
12
variable speed drives
Functions (continued)
Application functions
Operating speed range
Determinesthetwofrequencylimitswhichdenethespeedrangepermittedbythe
machineunderactualoperatingconditionswithinthespeciedtorquelimits.
LSP: Low speed, from 0 to HSP, factory setting 0
HSP: High speed, from LSP to 400 Hz, factory setting 50/60 Hz
Reference
5 V
10 V (external power supply)
20 mA
20 mA
Y mA
0 V
0 V
0 mA
4 mA
X mA
HSP
LSP
f (Hz)
Preset speeds
This is used to switch preset speed references.
Choice of between two and eight preset speeds.
Enabled by means of between 1 and 4 logic inputs.
Thepresetspeedsareadjustableinincrementsof0.1Hzfrom0Hzto400Hz.
They take priority over the reference given by the active control channel (analog
input or the navigation button).
The speed obtained with inputs
Llx and LIy at state 0 is LSP or the
speed reference, depending on
the level of analog input AI1.
Factory settings:
1
st
speed: LSP (low speed or
reference)
2
nd
speed: 10 Hz
3
rd
speed: 25 Hz
4
th
speed: 50 Hz
t
t
t
1
50
25
10
LIx 0
1
LIy 0
1
LI1 0
f (Hz)
LSP
Example of operation with 4 preset speeds
Three additional high speeds
ThesethreeadditionalhighspeedsaredenedbyHSP2,HSP3andHSP4.
They are used to select 2 or 4 high speeds (HSP/HSP2 or HSP/HSP2/HSP3/HSP4).
Enabling 2 or 4 high speeds requires the use of 1 or 2 logic inputs respectively.
Control modes
There are several control and reference channels which can be independent.
Commands (forward, reverse, etc.) and speed references can be sent via the
following channels:
v Terminals (logic and analog I/O)
v Local mode (STOP/RESET and RUN buttons and the navigation button)
v Remote display terminal
v Modbus
®
serial link
The control and reference channels can be separate (separate mode).
Example: The Run/Stop commands come from the terminals and the speed
reference comes from the Modbus serial link.
The control and reference channels can also come from the same source
(not separate mode).
Introduction:
page 8
Specications:
page 10
References:
page 14
Dimensions:
page 18
Connections:
page 22
Setting preset speeds with the SoMove setup software