PLSED309039EN PM1000 Series Power Meters
08/2010 Chapter 1 – PM1000 Series Power Meters Product Description
© 2010 Schneider Electric. All rights reserved.
The Indicators – Kilo, Mega, and Negative
Table 1-2 Indicators
Kilo: When lit, indicates that the reading is in Kilo (10
3
). 10,000 is displayed
as 10.00 K and 1.0 K as 1000.
Mega: When lit, indicates that the reading is in Mega, (10
6
). 10,000 K is
shown as 10.00 M. and 1.0 M as 1000 K.
Giga: When Kilo and Mega are lit together, the reading is in Giga (10
9
).
10,000 M is shown as 10.00 G and 1.0 G as 1000 M.
Negative: When lit, indicates that the reading is negative as per IEEE 100
and industry standard practice by meter-men:
When PF (power factor) is lead (capacitive load): Both PF and VAR
(reactive power) sign will be negative. When current is reversed: W (active
power) is negative.
Table 1-3: Giga, Mega (M), Kilo (K), and decimal point scaling
RMS readings are four digits. Energy readings have eight digits, including
four additional fractional digits. The maximum number the power meter
handles is 9,999 G for RMS and energy values.
This means that the energy readings of the power meter will overflow at
three values of Wh (active energy) or VAh (Apparent energy) (selectable
through PROG menu - setup) depending upon the PT (VT) and CT ratios
programmed.
Giga (k + M indicators ON)
Display shows Hi for positive numbers, Lo for negative numbers