Schneider Electric K series Bedienungsanleitung Seite 42

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 81
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 41
PM1000 Series Power Meters PLSED309039EN
Chapter 5 Installation 08/2010
42
© 2010 Schneider Electric. All rights reserved.
Setup System Type
The power meter needs to know the type of system to which it is connected
to. This information is programmed in the setup procedure, before using the
power meter. The power meter does allow you to change this setting while it
is running; however, this capability is meant for correcting a gross error, or
for training or educational purposes; it is not to be changed on regular basis.
The options are:
Wye/Star: For 3-phase 4-wire, three Watt-meter or three Element
circuits. Here, all three voltage phase signals, the neutral voltage
connection, and all three current input signals need to be wired in. This
means all the four voltage terminals, and six current terminals described in
the following section, need to be wired. For wye/star wiring configuration,
see 3-phase 4-wire WYE connection with 3 CTs and 3 PTs on page 43
for more information.
Delta: For 3-phase 3-wire, two Watt-meter or two Element circuits. For
delta and open delta wiring configuration, see 3-phase 3-wire Delta
connection with 2 CTs and 3 PTs and 3-Phase 3-Wire Open Delta
connection with 2 CTs and 2 PTs on page 44 for more information.
2-phase: For 2-phase 3-wire, two Watt-meter or two Element circuits.
Here, the two voltage phase signals, the neutral voltage connection, and
two current input signals need to be wired in. This means that the three
voltage terminals and four current terminals described in the following
section, need to be wired. For two phase wiring configuration, see 2-phase
3-wire connection with 2 CTs on page 45 for more information.
Single-phase: For single-phase 2-wire, one Watt-meter or one Element
circuits. Here a single voltage Phase signal, the neutral voltage
connection, and a single current input signal need to be wired in. This
means that two voltage terminals and one current terminal described in the
following section need to be wired. For Single phase wiring configuration,
see ―Single phase connection with 1 CT on page 45 for more information.
Seitenansicht 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 80 81

Kommentare zu diesen Handbüchern

Keine Kommentare