PLSED309039EN PM1000 Series Power Meters
08/2010 Chapter 6 Data Communication
© 2010 Schneider Electric. All rights reserved.
55
Block Parameter Address
Total RMS Block
Function Code: 03H Read
Number of registers: 20
No scaling required
Read as block only
Table 6-5: Total RMS block
Parameter
Description
Address
Type
PM1200
VA
Apparent power, total
3001
Float
W
Active power, total
3003
Float
VAR
Reactive power, total
3005
Float
PF
Average PF
3007
Float
VLL
Average line to line voltage
3009
Float
VLN
Average line to neutral voltage
3011
Float
A
Average current
3013
Float
F
Frequency, Hz
3015
Float
Reserved
Reserved
3017
Long
Intr
Number of interruption
3019
Long
R phase RMS Block:
Function Code: 03H Read
Number of registers: 20
No scaling required
Read as block only
Table 6-6: R phase RMS block
Parameter
Description
Address
Type
PM1200
VA1
Apparent power, phase1
3031
Float
W1
Active power, phase1
3033
Float
VAR1
Reactive power, phase1
3035
Float
PF1
Power factor, phase1
3037
Float
V12
Voltage phase1 to phase2
3039
Float
V1
Voltage phase1 to neutral
3041
Float
A1
Current, phase1
3043
Float
F1
Frequency, Hz
3045
Float
Reserved
Reserved
3047
Long
Intr1
Number of interruption
3049
Long
Seitenansicht 54