PM1000 Series Power Meters PLSED309039EN
Chapter 5 Installation 08/2010
40
© 2010 Schneider Electric. All rights reserved.
Voltage Signal Connections
For proper power meter operation, the voltage connection must be
maintained. The voltage must correspond to the correct terminal. The cable
required to terminate the voltage sense circuit should have an insulation
rating greater than 480 VAC and a current rating greater than 0.1 A.
There are four input voltage terminals marked V1, V2, V3, and Vn. See the
connection diagrams that follow, for details. For Delta connection, the Vn
terminal should be left unconnected.
PT Connections
The power meters directly accept LV voltage inputs of up to 480 VAC RMS
line to line (277 VLN). Voltages greater than this, typically HV systems,
must be connected through Potential transformers (PTs). The power meters
allow user programming of both PT primary and secondary voltages.
User programmable PT primary range: 0.1 to 999 kVAC RMS LL
User programmable PT secondary range: 80 to 481 VAC RMS LL
Power meter voltage Input burden: 0.2 VA per input
NOTE: The PT primary and secondary values must be user programmed before using the
power meter. Otherwise, the readings will be wrong.
Selecting the voltage fuses
We strongly recommend using fuses on each of the sense voltages (except
for neutral) and the control / auxiliary power.
Table 5-4: Fuse recommendation
Power Source
Source voltage
Fuse (A)
Line voltage
80 to 600 VLL
0.25
Auxiliary supply (Control
power)
0.25
Current Signal Connections
The power meter accepts up to 6 A AC RMS per channel directly. Above
that, a current transformer must be interposed to scale down the current.
There are three pairs of current input terminals marked A1, A2, and A3.
Each pair of input terminals is labeled as S1, S2 and has an arrow indicating
the direction of current flow. For proper measurements, the phase
identification, and the polarity of the current signals must be correct. The
forward flow (import by consumer) current direction must be into the S1
terminal and the exit from the S2 terminal. Maintain the correct sequence
and polarity to avoid wrong readings.
Any unused current input terminals must be shorted together, e.g., in Delta
connection, the terminals A2 (S1, S2) must be shorted together. The shorted
terminals do not need to be grounded.
Install the wiring for the current circuit at 480 VAC insulation as a minimum.
The cable connection should be rated for 7.5 A or greater and have a cross-
sectional area of 2.5 mm
2
(14 AWG) minimum.