PLSED309039EN PM1000 Series Power Meters
08/2010 Chapter 5 Installation
© 2010 Schneider Electric. All rights reserved.
37
Mounting
The power meters are panel mountable.
Table 5-2: Mounting
Description
Specification
Panel cut-out
92
+0.5
-0
mm
(w) x 92
+0.5
-0
mm(h) (3.62
+0.02
x
3.62
+0.02
in.)
IEC 61554 and DIN 43700
Panel thickness
0.5 to 4.0 mm (0.02 to 0.16 in.)
Instrumental bezel dimension
96 x 96 mm (3.78 x 3.78 in,)
Depth behind bezel
80 mm (3.15 in.) (82 mm (3.23 in.) with terminal
cover. Leave clearance for wires)
Mounting clamps screws
Slotted, two numbers
Terminal screws
Combination Phillips and Slotted head
The cut-out should be punched with the proper tool and should be free from
burrs. The following figure explains the mounting of the power meter.
Figure 5-2: Mounting
While supporting the power meter from the front, tighten both side clamp
screws in a criss-cross pattern till all slack is taken up and then apply one
full turn. Do not over-tighten. Over-tightening could result in breaking of the
clamps.
The power meter should be separated from other equipments and sufficient
space must be provided all around the power meter, to allow air to rise
vertically around the power meter. Lack of sufficient air for cooling may
result in over heating of the power meter.
NOTE: It is much easier to set up the meter before you mount the power meter on the panel.
See “Quick setup” on page 17 for more information.
2
Gently slide the power meter
through the cut-out.
3
Put the mounting clamps back in the power meter
and tighten the mounting clamps screws.
1
Remove the
mounting clamps
from the power
meter.