Installation Instruction 66571764GB3 Fire Detection 40
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
17. Configuration
Note! The panel is set to the configuration mode with configuration tool. This can be done also with the following
procedure.
Set control panel to access level 3.
1. Select with “MENU-button from main menu.
CURRENT ACCESS LEVEL:2
2. Press the wheel.
CHANGE TO ACCESS LEVEL 3:0000
3. Select the first digit with the wheel and press the wheel to
enter.
4. Repeat with the other digits.
5. Press “ENABLEwhen the right code is entered.
6. The panel is now in access level 3.
CURRENT ACCESS LEVEL: 3
7. Set panel to configuration state.
6. Set control panel to the configuration state by putting a
jumper in position “CONF” on the MC board. The display
shows the text:
CONFIGUARTION STARTED
READY FOR CONFIGURATION
7. Transfer the configuration.
8. Connect configuration cable to the terminal RS232.
9. Configure the control panel with the configuration tool
10. Remove the configuration cable from the terminal RS232
and the jumper from the position “CONF” on the MC.
Restart the panel.
11. Restart the control panel by pressing “RESET” button on the
MC.