Installation Instruction 66571764GB3 Fire Detection 26
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
show it as fault warning.
MAINTENANCE 67: (r)
Saturation of infrared detector at CoPTIR/PTIR sensor
MAINTENANCE 68: (r)
80% of drift limit (when “report dirty detector” requested)
MAINTENANCE 69: (r)
99% of drift limit (when “report dirty detector” requested)
FAULT 70: (r)
Undefined fault code from ALC/SySeAp device.
FAULT 71: (r)
Memory write operation of the device failed
FAULT 72: (r)
Memory read operation of the device failed
FAULT 73: (r)
Communication troubles with device.
FAULT 74: (r)
Self test of the detector failed.
FAULT 75: (r)
Beam sensor CPU fault
FAULT 76: (r)
Beam sensor align targeting
FAULT 77: (r)
Beam sensor general fault
FAULT 78: (r)
Beam sensor signal too high
FAULT 79: (r)
cell life expiration of CoPTIR sensor
FAULT 80: (r)
The SW of ALC board is not compatible for desired sounder mode
FAULT 81: (r)
Input module has been configured as "fire router fault". When module
alarms FX show it as fault warning.
FAULT 82: (r)
Input module has been configured as "VACIE fault". When module
alarms FX show it as fault warning.
FAULT 83: (r)
Unsupported address device has been configured to the loop of LC board
(The SW of LC is older than configuration made with WinFXNet).
FAULT 84: (r)
Power failure of supervised output circuit of a module
FAULT 85: (r,s)
The OEM code of the device is not Esmi/Pelco code.
FAULT 86: (r)
The control of output of SySeAp device did not work
FAULT 87: (?)
MAINT 88: (?)
MAINT 89: (?)
FAULT 90: (r,s)
Unacceptable device
ALC: detector is not Intellia, device is XP95 but not configured
MAINTENANCE 91: (r)
FAULT 92: (r)
break in input line of the CLC unit
FAULT 93: (r)
short circuit in input line of the CLC unit
FAULT 94: (r)
voltage problem in input line of the CLC unit
FAULT 95: (r)
Voice evacuation mute input active time expired
FAULT 96: (?)
MAINTENANCE 98: (r)
simulated maintenance (service command)
FAULT 99: (r)
simulated fault (service command)
s = start up phase when scanning devices (after panel (re)start or when is loop connected by user)
r = running time when device is normally monitored
c = loop is configured with PC
n = loop is not configured
Note !
Fault delays / timeouts
Reason for Fault 52 ( no PW1 received) must be active for 99sec. before the fault is shown.
Delay for fault 63 (PW4 out of limits) is 30 sec. if any good pulses are received, counter will stop, and if
no bad pulses with in 10sec, the counter is reset