Installation Instruction 66571764GB3 Fire Detection 26
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571764GB3 16 2012
© 2009 Schneider Electric. All rights reserved.
show it as fault warning.
− Saturation of infrared detector at CoPTIR/PTIR sensor
− 80% of drift limit (when “report dirty detector” requested)
− 99% of drift limit (when “report dirty detector” requested)
− Undefined fault code from ALC/SySeAp device.
− Memory write operation of the device failed
− Memory read operation of the device failed
− Communication troubles with device.
− Self test of the detector failed.
− Beam sensor align targeting
− Beam sensor general fault
− Beam sensor signal too high
− cell life expiration of CoPTIR sensor
− The SW of ALC board is not compatible for desired sounder mode
− Input module has been configured as "fire router fault". When module
alarms FX show it as fault warning.
− Input module has been configured as "VACIE fault". When module
alarms FX show it as fault warning.
− Unsupported address device has been configured to the loop of LC board
(The SW of LC is older than configuration made with WinFXNet).
− Power failure of supervised output circuit of a module
− The OEM code of the device is not Esmi/Pelco code.
− The control of output of SySeAp device did not work
− Unacceptable device
ALC: detector is not Intellia, device is XP95 but not configured
− break in input line of the CLC unit
− short circuit in input line of the CLC unit
− voltage problem in input line of the CLC unit
− Voice evacuation mute input active time expired
− simulated maintenance (service command)
− simulated fault (service command)
s = start up phase when scanning devices (after panel (re)start or when is loop connected by user)
r = running time when device is normally monitored
c = loop is configured with PC
n = loop is not configured
Note !
Fault delays / timeouts
Reason for Fault 52 ( no PW1 received) must be active for 99sec. before the fault is shown.
Delay for fault 63 (PW4 out of limits) is 30 sec. if any good pulses are received, counter will stop, and if
no bad pulses with in 10sec, the counter is reset