9.2 Battery connection
1. Install the batteries in the cabinet. Check that the battery
cable is disconnected from the battery terminal BATT.
P
O
2
+
2
4
V
-
P
O
1
+
2
4
V
-
B
A
T
T
+
-
2. Check battery polarity from the markings on the battery.
3. Connect the battery cables to the poles as follows:
The batteries are 12 V batteries. If two batteries are used,
they are connected in series.
If four batteries are used, two series connected pairs are
connected in parallel (Voltage is 24 VDC).
4. Connect the battery cable to the battery terminal BATT on
the PS component board.
WARNING!
Connecting the batteries in the wrong way
may cause a short circuit in the batteries,
which may lead to an explosion, a strong
electric arc or fire in the battery cables.
5. Reset the battery fault indication in the control panel by
pressing the “RESET”- button until the pulsed audible
The “FAULT”- led goes out.
The display shows the text:
FX
Fire Panel
Activate menu by pressing wheel