10.2 Cable table
Cable connection
Comments
Addressable detection
circuit cables, SLC- loop
shield
2 x 1.0 mm
2
+
(60 Ω)
1600 m
The cable resistance of the loop is max. 60 Ω and the
capacitance max. 180 nF between conductor and shield, 360
nF between conductors. Max. voltage drop is 6 V.
Addressable detection
circuit cables, ALC- loop
shield
2 x 1.0 mm
2
+
(60 Ω)
1500 m
The cable resistance of the loop is max. 60 Ω and the
capacitance max. 180 nF between conductor and shield, 360nF
between conductors. Max. voltage drop is 9 V.
Conventional detection
circuit cables, CLC- line
shield
2 x 1.0 mm
2
+
(100 Ω)
2400 m
The cable resistance of the loop is max. 50Ω, if an Exi barrier is
connected to the loop, otherwise max 100Ω.
The max. allowed capacitance of the cable is 0.5µF.
Sub-detection circuits of
conventional zone
modules, SLC- loop
circuits of
conventional
1200 m
(100 Ω)
Conventional zone module EM210E-CZ, EM210E-CZR,
M512ME and conventional detectors or conventional manual
call points.
Sub-detection circuits of
conventional zone
modules, ALC- loop
circuits of
conventional
600m
(50 Ω)
Conventional zone module EMI-310-CZ / EMI410-CZ and
conventional detectors or conventional manual call points.
Power supply to
conventional zone
modules
shield
2 x 1.0 mm
2
+
(50 Ω)
1200 m
Cable resistance max. 50 Ω.
Conventional Exi-area
sub-loop unit
2 x 0.5 mm
2
+
shield
2 x 1.0 mm
2
+
shield
625 m
(50 Ω)
1200 m
(50 Ω)
From panel through the address module to the Eex barrier
resistance max. 50 Ω total. If power supply is brought to several
units through the same cable, the real length of this part must
be multiplied with the number of units when comparing with the
150 m
Loop resistance from the Exi-barrier to most distant detector
max.12 Ω. Loop capacitance max. 390 nF.
Printer connection
- Serial data
15 m RS232
- INFO
3 x 0.5 mm
2
+
shield
1000 m RS485
Serial connections
between FX NET
panels, 2 serial line
System1 line
System2 line
4 x 0.5 mm
2
+
shield
Cable 2:
4 x 0.5 mm
2
+
1000 m
1000 m
2 X RS 485
Note!
Isolated Gnd terminals in RS485 Serial connection must be
connected between the panels using signal wire not shield.
FX clean contact input
lines
2 x 0.5 mm
2
2000 m
FX clean contact output
lines
2 x 0.5 mm
2
or
2 x 1.0 mm
2
To be
calculated
separately
The equipment receiving the contact signal may have
restrictions on cable properties.
Load controlled by the relay output may restrict allowed
resistance and length per cross section.
Relay contact rating is 30 VDC 1 A
lines – fire bell, sounder
line
2 x 0.5 mm
2
or
2 x 1.0 mm
2
or
2 x 2.5 mm
2
To be
calculated
separately
Max. allowed voltage drop defines cable to be used.
modules, SLC- loop
2 x 0.5 mm
2
+
shield
625 m
(50 Ω)
Monitor modules M500ME, M503ME, M501ME,
EM210E, EM220E, EM221E.
modules, SLC- loop
2 x 1.5 mm
2
or
2
calculated
Control modules M500CHE, EM201E, EM221E, M201 and
M240.
Number and distances of the relay control modules define the