Elements of Network Planning
890 USE 100 00
51
2.2.5 Modbus Plus Network Grounding
Each tap has a grounding screw for connection to the site panel ground.
Modicon drop cables have a grounding lug in the cable package. This
must be installed on the cable and connected to the grounding screw on
the tap.
The node device end of the drop cable has a lug which must be
connected to the node device’s panel ground. The network cable must
be grounded through this connection at each node site, even when the
node device is not present. The ground point must not be left open. No
other grounding method can be used.
For a full description of Modicon controller system grounding
requirements, refer to the documents listed in the Related Publications
section of this guide.