Estimating Network Performance
890 USE 100 00
101
Caution: In the worst-case timing for this event, as much as
15 s can be required for the ring to be reconstituted with the
nodes in place at their new addresses. This can occur in a
network of any size, if node address 64 is one of the nodes
attempting to join at the same moment that the message
counter and next-try addresses are both at a value of 1.
In most cases the time will be significantly less than this
maximum amount, however the network planner should
account for this worst-case event in the design of the network
layout and programming of the node applications.