5—I/O MENU
This menu allows you to assign functions to the inputs and outputs. It is
accessible when the access locking switch is in the position. The
I/O assignments can only be modified if the motor is not running.
The inputs and outputs displayed in the I/O menu vary depending on
selections made in the 4
—Control menu and whether or not an I/O
extension card is installed. The default settings depend on the macro-
configuration selected (see Table 3 on page 22 for factory settings).
Table 15 shows which functions can be assigned to the analog input and
which can be assigned to a logic input. Additional inputs are available and
can be assigned when an I/O extension card is installed. LI1 and R1
cannot be reassigned. AI1, LI1, and R1 are not displayed in the I/O menu.
Table 15: Possible Assignments for Configurable Inputs
I/O Extension Card
2 Logic
Inputs
LI5-LI6
Analog
Input
AI3
Logic
Input
[1]
A, A-,
B, B-
Drive Controller without an I/O Extension Card
Analog
Input
AI2
3 Logic
Inputs
LI2–LI4
Code and
Parameter
Description
NO: Not assigned Not assigned X X X X
RV: Reverse Run reverse X
RP2: Switch ramp2 Ramp switching X
JOG Jog X
+SP: + Speed +Speed X
-SP: - Speed -Speed X
PS2: 2 preset Sp 2 preset speeds X
PS4: 4 preset Sp 4 preset speeds X
PS8: 8 preset Sp 8 preset speeds X
NST: Freewhl Stop Freewheel stop/Run permissive X
DCI: DC inject DC injection braking X
FST: Fast stop Fast stop X
CHP: Multi.Motor Switching between two motors X
TL2: Torque Lim2 Second torque limit X
[1]
The menu for assigning encoder input A, A-, B, B- is called “Assign AI3”.
[2]
To configure an AI for PIF: PI regulator, RFC: Auto/manual must not be assigned to
a logic input.
Menu
5
NOTE: When
reassigning inputs
from +Speed and
-Speed, reassign
-Speed first.
When reassigning
inputs from preset
speeds, reassign
PS8 first then PS4,
then PS2.