ALTIVAR
58 Keypad Display VVDED397047US R8/01
Chapter 2 Menus 08/01
22
© 19982001 Schneider Electric All Rights Reserved
Transferring a file created for a drive controller without an I/O extension
card to a drive controller with an I/O extension card may result in
unexpected I/O assignment. Verify all I/O assignments. It is
recommended that I/O functions not used in the application be
un-assigned.
Table 3: Drive Controller I/O Assignments
Hdg: Material
Handling
[1]
GEn: General Use
VT: Variable
Torque
Logic Input LI1 Forward Forward Forward
Logic Input LI2 Reverse Reverse Reverse
Logic Input LI3 2 Preset speeds Jog Auto/manual
Logic Input LI4 4 Preset speeds Freewheel stop
[2]
DC injection braking
Analog Input AI1 Reference summing Reference summing Speed reference 1
Analog Input AI2 Reference summing Reference summing Speed reference 2
Relay R1 Drive fault relay Drive fault relay Drive fault relay
Relay R2 Not assigned Not assigned Not assigned
[1]
Factory default setting.
[2]
If the Freewheel Stop/Run Permissive function is configured, the drive controller will
not start the motor unless the logic input is connected to +24 V.
Table 4: I/O Extension Card Factory Presets
Hdg: Material
Handling
GEn: General Use VT: Variable Torque
Logic Input LI5 8 preset speeds Fault reset Freewheel stop
[1]
Logic Input LI6 Fault reset
Current limit
[2]
or
Torque limit 2
[3]
Ramp switching
Analog Input AI3
[2]
or Logic Inputs A,
A-, B, B-
[3]
Reference summing
[2]
Reference summing
[2]
PI regulator feedback
[2]
Speed feedback Speed feedback Speed feedback
Logic Output LO Current level attained
Output contactor
command
High speed attained
Analog Output AO Motor frequency Motor frequency Motor frequency
[1]
If the Freewheel Stop / Run Permissive function is configured, the drive controller will
not start the motor unless the logic input is connected to +24 V.
[2]
With analog I/O extension card (VW3A58201U).
[3]
With digital I/O extension card (VW3A58202U).
Note: LI1, AI1,
and R1
assignments are
not visible in the
5I/O menu.
LI1 and R1
cannot be
reassigned.
Note: You must
ensure that the
functions which
are
programmed
are compatible
with the control
scheme used.