ALTIVAR
58 Keypad Display VVDED397047US R8/01
Chapter 2 — Menus 08/01
42
© 1998–2001 Schneider Electric All Rights Reserved
Type of stop
Stt
Type of stop:
When a stop is requested, the type of
STN–FST
NST–DCI
STN
stop is activated until the FFt threshold (2—Adjust menu) is reached.
Below this threshold, freewheel stop is activated.
Stn: On decel ramp
Fst: Fast stop
Nst: Freewheel stop
Dci: DC injection stop
Ramp Type
rPt
Defines the type of acceleration and
deceleration ramps.
LIN: linear S: S ramp U: U ramp
LIN - S - U LIN
Table 11: 3—Drive Menu Parameters (Continued)
Parameter Code Description
Adjustment
Range
Factory
Setting
[1]
Depending on the position of the 50/60 Hz switch. Ensure that the switch setting
matches the input frequency (see page 13).
[2]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.
[3]
The factory setting depends on the macro-configuration used: No for Material Handling,
Yes for General Use and Variable torque.
[4]
Refer to the drive controller instruction bulletin, VVDED397048US, for duty cycle ratings
of the drive controllers.
★ These parameters are available only with the I/O extension card installed.
Menu
3
NOTE: This
parameter, Stt,
cannot be
accessed if the
R2 relay or a
logic output is
assigned to the
“BLC: Brake
Logic” function.
50/60
Time
0
1/5
ACC/deC
ACC/deC
Motor
Frequency (Hz)
1/5
ACC/deC
S ramp
fn
f (Hz)
t
fn
f (Hz)
t
T1
T1
U Ramp
Acc
T1 = 1/Acc
Dec
T1 = 1/Dec