Schneider Electric Mupgrade Utility Installationsanleitung Seite 1

Stöbern Sie online oder laden Sie Installationsanleitung nach Software Schneider Electric Mupgrade Utility herunter. Schneider Electric Mupgrade Utility Installation guide Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 130
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen

Inhaltsverzeichnis

Seite 1 - Conext™ Configuration

AC1AC2EventEqualizekWACharging!InvertingConext™ Configuration ToolOwner’s GuideVersion 1.00www.SEsolar.com

Seite 2 - AT WWW.SESOLAR.COM

Contentsx 975-0720-01-01This manual is for use by qualified personnel onlyGrid Tie Configuration - - - - - - - - - - - - - - - - - - - - - - - - - - -

Seite 3 - About This Guide

Configuring the System Control Panel975-0720-01-01 3–35This manual is for use by qualified personnel onlyBasic ConfigurationBasic configuration includ

Seite 4 - Disclaimer

Device Configuration3–36 975-0720-01-01This manual is for use by qualified personnel onlySaving and Restoring ConfigurationsSave Configuration allows

Seite 5 - Important Safety Instructions

Configuring the Conext Battery Monitor975-0720-01-01 3–37This manual is for use by qualified personnel onlyBasic StatusThe Basic Status window shows t

Seite 6 - Safety Information

Device Configuration3–38 975-0720-01-01This manual is for use by qualified personnel onlyBattery ConfigurationBattery configuration allows you to conf

Seite 7

Configuring the Conext Battery Monitor975-0720-01-01 3–39This manual is for use by qualified personnel onlyBattery Temperature ConfigurationBattery te

Seite 8 - OPERATION

Device Configuration3–40 975-0720-01-01This manual is for use by qualified personnel onlyHardware ConfigurationHardware configuration allows you to co

Seite 9 - Contents

Configuring the Conext Battery Monitor975-0720-01-01 3–41This manual is for use by qualified personnel onlyMulti-Unit ConfigurationMulti-unit configur

Seite 10 - 4 System Logging

Device Configuration3–42 975-0720-01-01This manual is for use by qualified personnel onlyModbus ConfigurationBattery Monitor Modbus settings are confi

Seite 11 - Legacy USB-to-Xanbus Adapters

975-0720-01-01 4–1This manual is for use by qualified personnel only4 System LoggingChapter 4, “System Logging” contains information and procedures to

Seite 12 - 1 Introduction and

System Logging4–2 975-0720-01-01This manual is for use by qualified personnel onlyIntroductionWith the system logging feature you can log any paramete

Seite 13

Contents975-0720-01-01 xiThis manual is for use by qualified personnel onlyUsing the Data - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Seite 14 - Inside the Box

Configuration975-0720-01-01 4–3This manual is for use by qualified personnel onlyConfigurationThe logging configuration is displayed as a tree. The ma

Seite 15

System Logging4–4 975-0720-01-01This manual is for use by qualified personnel onlyPolling PeriodYou can set the logging period in seconds using a drop

Seite 16

Configuration975-0720-01-01 4–5This manual is for use by qualified personnel onlyEmail OptionsOnce a log is complete, Conext Configuration Tool can au

Seite 17

System Logging4–6 975-0720-01-01This manual is for use by qualified personnel onlyTroubleshootingGetting Conext Configuration Tool to send an email ca

Seite 18

Running the Logger975-0720-01-01 4–7This manual is for use by qualified personnel onlyPassive ModeFTP normally uses two connections, one initiated fro

Seite 19

System Logging4–8 975-0720-01-01This manual is for use by qualified personnel onlyLimitationsThere is no particular limit to the number of data points

Seite 20 - OF ELECTRIC SHOCK

Using the Data975-0720-01-01 4–9This manual is for use by qualified personnel onlyTupleThe Tuple line is used only for fields within variable length m

Seite 21 - Included Xanbus cable

System Logging4–10 975-0720-01-01This manual is for use by qualified personnel only

Seite 22 - Conext XW SCP

975-0720-01-01 5–1This manual is for use by qualified personnel only5 Upgrading FirmwareChapter 5, “Upgrading Firmware” contains information about upg

Seite 23

Upgrading Firmware5–2 975-0720-01-01This manual is for use by qualified personnel onlyIntroductionThe firmware upgrade feature allows Conext Configura

Seite 24

975-0720-01-01 1–1This manual is for use by qualified personnel only1 Introduction and InstallationChapter 1, “Introduction and Installation” introduc

Seite 25

Starting Firmware Upgrade975-0720-01-01 5–3This manual is for use by qualified personnel onlyTo upgrade Conext Configuration Tool firmware:1. Power do

Seite 26 - USB-to-Xanbus Adapter Status

Upgrading Firmware5–4 975-0720-01-01This manual is for use by qualified personnel onlyAfter clicking Upgrade, progress bars for each device will be di

Seite 27

975-0720-01-01 A–1This manual is for use by qualified personnel onlyA Legacy USB-to-Xanbus AdaptersAppendix A, “Legacy USB-to-Xanbus Adapters” provid

Seite 28 - Control Menu Features

Legacy USB-to-Xanbus AdaptersA–2 975-0720-01-01This manual is for use by qualified personnel onlyInstalling Previous Versions of the USB-to-Xanbus Ada

Seite 29 - Configure Menu Features

Installing Previous Versions of the USB-to-Xanbus Adapter975-0720-01-01 A–3This manual is for use by qualified personnel onlyWindows XPTo install usin

Seite 30 - Temperature Units

Legacy USB-to-Xanbus AdaptersA–4 975-0720-01-01This manual is for use by qualified personnel only3. Select Search for the best driver in these locatio

Seite 31 - Restore Configuration

Installing Previous Versions of the USB-to-Xanbus Adapter975-0720-01-01 A–5This manual is for use by qualified personnel only3. Click on the Start but

Seite 32 - View Menu Functions

Legacy USB-to-Xanbus AdaptersA–6 975-0720-01-01This manual is for use by qualified personnel onlyWindows 8To install using Windows 8:1. Open the Charm

Seite 33 - 1–22 975-0720-01-01

Installing Previous Versions of the USB-to-Xanbus Adapter975-0720-01-01 A–7This manual is for use by qualified personnel only2. Click the Update and R

Seite 34 - 2 System

Legacy USB-to-Xanbus AdaptersA–8 975-0720-01-01This manual is for use by qualified personnel only4. Click Advanced Options, followed by Windows Startu

Seite 35

Introduction and Installation1–2 975-0720-01-01This manual is for use by qualified personnel onlyIntroducing Conext Configuration ToolConext Configura

Seite 36

Printed in ChinaSchneider Electricwww.SEsolar.com For other country details please contact your local Schneider Electric Sales Representative or visit

Seite 37 - Quick Configuration Method

Introducing Conext Configuration Tool975-0720-01-01 1–3This manual is for use by qualified personnel onlyInside the BoxThe following items are include

Seite 38

Introduction and Installation1–4 975-0720-01-01This manual is for use by qualified personnel only❐ Xanbus network cable (14 ft./4.25 m)❐ Installation

Seite 39

Installing Conext Configuration Tool975-0720-01-01 1–5This manual is for use by qualified personnel onlyInstalling Conext Configuration ToolTo install

Seite 40

Introduction and Installation1–6 975-0720-01-01This manual is for use by qualified personnel onlyConnecting the USB-to-Xanbus Adapter to Your Computer

Seite 41

Installing Conext Configuration Tool975-0720-01-01 1–7This manual is for use by qualified personnel only3. Under Device Type, select USB.4. Click OK.T

Seite 42

Introduction and Installation1–8 975-0720-01-01This manual is for use by qualified personnel only6. The internal serial number of the USB-to-Xanbus ad

Seite 43

Copyright and ContactCopyright © 2012, 2014 Schneider Electric. All Rights Reserved.All trademarks are owned by Schneider Electric Industries SAS or i

Seite 44

Installing Conext Configuration Tool975-0720-01-01 1–9This manual is for use by qualified personnel onlyConnecting the USB-to-Xanbus Adapter to the Xa

Seite 45

Introduction and Installation1–10 975-0720-01-01This manual is for use by qualified personnel onlyNote: Ensure that the USB-to-Xanbus adapter pins are

Seite 46

Installing Conext Configuration Tool975-0720-01-01 1–11This manual is for use by qualified personnel onlyNetwork terminationThe Xanbus network must be

Seite 47

Introduction and Installation1–12 975-0720-01-01This manual is for use by qualified personnel onlyInstalling the Conext Configuration Tool SoftwareTo

Seite 48 - Detailed Configuration Method

Installing Conext Configuration Tool975-0720-01-01 1–13This manual is for use by qualified personnel only7. Add a desktop icon by clicking on the appr

Seite 49

Introduction and Installation1–14 975-0720-01-01This manual is for use by qualified personnel only11. An information screen appears, as shown below.To

Seite 50

Operating Conext Configuration Tool975-0720-01-01 1–15This manual is for use by qualified personnel onlyOperating Conext Configuration ToolUSB-to-Xanb

Seite 51

Introduction and Installation1–16 975-0720-01-01This manual is for use by qualified personnel only3. Configure the Conext Automatic Generator Start. S

Seite 52

Operating Conext Configuration Tool975-0720-01-01 1–17This manual is for use by qualified personnel only•Perform Firmware Upgrades• Convert Phase of y

Seite 53

Introduction and Installation1–18 975-0720-01-01This manual is for use by qualified personnel onlyChargeUse this feature to enable or disable charging

Seite 54

About This Guide975-0720-01-01 iiiThis manual is for use by qualified personnel onlyAbout This GuidePurposeThe purpose of this Owner’s Guide is to pro

Seite 55

Operating Conext Configuration Tool975-0720-01-01 1–19This manual is for use by qualified personnel only3. To read the current names, click the Read b

Seite 56

Introduction and Installation1–20 975-0720-01-01This manual is for use by qualified personnel onlyFirmware UpgradeTo upgrade the firmware in a device,

Seite 57

Operating Conext Configuration Tool975-0720-01-01 1–21This manual is for use by qualified personnel onlyView Menu FunctionsSystem MapTo view the Syste

Seite 58

Introduction and Installation1–22 975-0720-01-01This manual is for use by qualified personnel only

Seite 59

975-0720-01-01 2–1This manual is for use by qualified personnel only2 System ConfigurationChapter 2 contains information and procedures to configure a

Seite 60

System Configuration2–2 975-0720-01-01This manual is for use by qualified personnel onlyAbout the Configuration WizardsThe Conext Configuration Tool C

Seite 61

Using the Configuration Wizard975-0720-01-01 2–3This manual is for use by qualified personnel onlyUsing the Configuration Wizard1. Start the Configura

Seite 62

System Configuration2–4 975-0720-01-01This manual is for use by qualified personnel onlyQuick Configuration Method1. Reset devices to factory defaults

Seite 63

Using the Configuration Wizard975-0720-01-01 2–5This manual is for use by qualified personnel onlyIf possible, take note of which units are assigned w

Seite 64 - Restoring a Configuration

System Configuration2–6 975-0720-01-01This manual is for use by qualified personnel onlySetting the connections for a Xanbus-enabled device provides a

Seite 65

About This Guideiv 975-0720-01-01This manual is for use by qualified personnel onlyChapter 3, “Device Configuration” describes how to use Conext Confi

Seite 66 - 3 Device

Using the Configuration Wizard975-0720-01-01 2–7This manual is for use by qualified personnel onlyTo configure a single-phase unit in a single-phase c

Seite 67 - Configuring Devices

System Configuration2–8 975-0720-01-01This manual is for use by qualified personnel onlyConfiguring Split Phase Master and Slave DevicesIf you chose t

Seite 68 - Configuration Commands

Using the Configuration Wizard975-0720-01-01 2–9This manual is for use by qualified personnel onlyf) When selection is finished, click Next. Proceed t

Seite 69 - OF ELECTRIC SHOCK OR FIRE

System Configuration2–10 975-0720-01-01This manual is for use by qualified personnel onlyi) When selection is finished, click Next. Proceed to Set the

Seite 70

Using the Configuration Wizard975-0720-01-01 2–11This manual is for use by qualified personnel only6. Set the Conext XW Inverter/Charger Custom Batter

Seite 71 - Inverter Configuration

System Configuration2–12 975-0720-01-01This manual is for use by qualified personnel onlyTable 2-2 XW Inverter/Charger Custom Battery SettingsSetting

Seite 72

Using the Configuration Wizard975-0720-01-01 2–13This manual is for use by qualified personnel only7. Set the Solar Charge Controller Charger Settings

Seite 73 - Charger Configuration

System Configuration2–14 975-0720-01-01This manual is for use by qualified personnel only8. Set the Solar Charge Controller Custom Battery Settings. (

Seite 74

Using the Configuration Wizard975-0720-01-01 2–15This manual is for use by qualified personnel only9. Save the System Configuration.If necessary, you

Seite 75 - AC Transfer Configuration

System Configuration2–16 975-0720-01-01This manual is for use by qualified personnel onlyThe network requires that each device of the same type have a

Seite 76

Safety975-0720-01-01 vThis manual is for use by qualified personnel onlyImportant Safety InstructionsREAD AND SAVE THESE INSTRUCTIONS - DO NOT DISCAR

Seite 77 - Grid Tie Configuration

Using the Configuration Wizard975-0720-01-01 2–17This manual is for use by qualified personnel only3. Set the AC and DC connections for all devices.Se

Seite 78

System Configuration2–18 975-0720-01-01This manual is for use by qualified personnel only5. Set the XW Inverter/Charger Inverter Settings.Figure 2-20

Seite 79

Using the Configuration Wizard975-0720-01-01 2–19This manual is for use by qualified personnel only6. Set the XW Inverter/Charger Settings.Figure 2-21

Seite 80

System Configuration2–20 975-0720-01-01This manual is for use by qualified personnel only7. Set the Conext XW+ Inverter/Charger Custom Battery Setting

Seite 81

Using the Configuration Wizard975-0720-01-01 2–21This manual is for use by qualified personnel only8. Set the XW Inverter/Charger AC Settings.AC Setti

Seite 82

System Configuration2–22 975-0720-01-01This manual is for use by qualified personnel only9. Set the XW Inverter/Charger Grid Support Settings.The Grid

Seite 83 - 3–18 975-0720-01-01

Using the Configuration Wizard975-0720-01-01 2–23This manual is for use by qualified personnel onlyFigure 2-25 Setting the XW Inverter/Charger Grid Su

Seite 84

System Configuration2–24 975-0720-01-01This manual is for use by qualified personnel only10. Set the XW Solar Charge Controller Charger settings.Load

Seite 85

Using the Configuration Wizard975-0720-01-01 2–25This manual is for use by qualified personnel only11. Set the XW Solar Charge Controller Custom Batte

Seite 86 - Solar Charge Controllers

System Configuration2–26 975-0720-01-01This manual is for use by qualified personnel only12. Set the XW Solar Charge Controller Input Settings.The inp

Seite 87

Safetyvi 975-0720-01-01 This manual is for use by qualified personnel onlySafety Information1. Before using the Conext SW/XW/XW+ inverter, read all in

Seite 88 - Thermal Status

Using the Configuration Wizard975-0720-01-01 2–27This manual is for use by qualified personnel onlyMulti-Cluster Configuration MethodTo configure a mu

Seite 89

System Configuration2–28 975-0720-01-01This manual is for use by qualified personnel onlyyou want to be the phase master into the master boxes for eac

Seite 90

Using the Configuration Wizard975-0720-01-01 2–29This manual is for use by qualified personnel only5. A Battery Cluster Warning will appear advising t

Seite 91 - Solar Input Configuration

System Configuration2–30 975-0720-01-01This manual is for use by qualified personnel only8. If Custom was selected as Battery Type, set the Conext XW

Seite 92 - Advanced Features

Restoring a Configuration975-0720-01-01 2–31This manual is for use by qualified personnel only10. Set the Conext XW+ AC Settings as outlined in Step 8

Seite 93

System Configuration2–32 975-0720-01-01This manual is for use by qualified personnel onlyFiles that appear in red are incompatible with your system. T

Seite 94 - Generator Configuration

975-0720-01-01 3–1This manual is for use by qualified personnel only3 Device ConfigurationChapter 3, “Device Configuration” describes how to use Conex

Seite 95

Device Configuration3–2 975-0720-01-01This manual is for use by qualified personnel onlyConfiguring DevicesYou can use Conext Configuration Tool to co

Seite 96 - Trigger Configuration

Configuring Devices975-0720-01-01 3–3This manual is for use by qualified personnel onlyConfiguration CommandsEvery configuration dialog box includes t

Seite 97

Device Configuration3–4 975-0720-01-01This manual is for use by qualified personnel onlySaving the System ConfigurationYou can save the current system

Seite 98 - Multi-Unit AGS Configuration

Safety975-0720-01-01 viiThis manual is for use by qualified personnel onlyDANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH• Apply appropriate

Seite 99

Configuring Conext XW+ and Conext SW Inverter/Chargers975-0720-01-01 3–5This manual is for use by qualified personnel onlyThe following setting catego

Seite 100 - Basic Configuration

Device Configuration3–6 975-0720-01-01This manual is for use by qualified personnel onlyInverter ConfigurationInverter configuration includes enabling

Seite 101

Configuring Conext XW+ and Conext SW Inverter/Chargers975-0720-01-01 3–7This manual is for use by qualified personnel onlyTable 3-1 Inverter Settings

Seite 102 - Basic Status

Device Configuration3–8 975-0720-01-01This manual is for use by qualified personnel onlyCharger ConfigurationCharger Configuration gives you options f

Seite 103 - Battery Configuration

Configuring Conext XW+ and Conext SW Inverter/Chargers975-0720-01-01 3–9This manual is for use by qualified personnel onlyBattery ConfigurationBattery

Seite 104

Device Configuration3–10 975-0720-01-01This manual is for use by qualified personnel onlyAC Transfer ConfigurationAC Transfer configures the voltage a

Seite 105

Configuring Conext XW+ and Conext SW Inverter/Chargers975-0720-01-01 3–11This manual is for use by qualified personnel onlyFigure 3-9 Inverter/Charger

Seite 106 - Multi-Unit Configuration

Device Configuration3–12 975-0720-01-01This manual is for use by qualified personnel onlyGrid Tie ConfigurationThe Grid Tie Configuration window sets

Seite 107 - Modbus Configuration

Configuring Conext XW+ and Conext SW Inverter/Chargers975-0720-01-01 3–13This manual is for use by qualified personnel onlyFigure 3-10 Inverter/Charge

Seite 108

Device Configuration3–14 975-0720-01-01This manual is for use by qualified personnel onlyGenerator Support ConfigurationConext XW+ only: Generator sup

Seite 109 - Getting Started

Safetyviii 975-0720-01-01 This manual is for use by qualified personnel onlyDANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH• Battery Circuit B

Seite 110 - Configuration

Configuring Conext XW+ and Conext SW Inverter/Chargers975-0720-01-01 3–15This manual is for use by qualified personnel onlyGenerators have a limited o

Seite 111 - Automatic restart

Device Configuration3–16 975-0720-01-01This manual is for use by qualified personnel onlyFigure 3-12 XW Inverter/Charger Auxiliary Output Configuratio

Seite 112 - Email Options

Configuring Conext XW+ and Conext SW Inverter/Chargers975-0720-01-01 3–17This manual is for use by qualified personnel onlyFigure 3-13 XW Inverter/Cha

Seite 113

Device Configuration3–18 975-0720-01-01This manual is for use by qualified personnel onlyFigure 3-15 XW Inverter/Charger Auxiliary Output Configuratio

Seite 114 - Running the Logger

Configuring Conext XW+ and Conext SW Inverter/Chargers975-0720-01-01 3–19This manual is for use by qualified personnel onlyMulti-Unit ConfigurationMul

Seite 115 - Using the Data

Device Configuration3–20 975-0720-01-01This manual is for use by qualified personnel onlyAdvanced Features ConfigurationAdvanced Features Configuratio

Seite 116 - Date and Time

Configuring Conext MPPT 80 600 and Conext MPPT 60 150 Solar Charge Controllers975-0720-01-01 3–21This manual is for use by qualified personnel onlySav

Seite 117 - 4–10 975-0720-01-01

Device Configuration3–22 975-0720-01-01This manual is for use by qualified personnel onlyBasic StatusThe Basic Status window displays input and output

Seite 118 - 5 Upgrading

Configuring Conext MPPT 80 600 and Conext MPPT 60 150 Solar Charge Controllers975-0720-01-01 3–23This manual is for use by qualified personnel onlyThe

Seite 119 - Starting Firmware Upgrade

Device Configuration3–24 975-0720-01-01This manual is for use by qualified personnel onlyCharger ConfigurationCharger Configuration gives you options

Seite 120

Contents975-0720-01-01 ixThis manual is for use by qualified personnel only1 Introduction and InstallationIntroducing Conext Configuration Tool - - -

Seite 121 - Upgrade Failures

Configuring Conext MPPT 80 600 and Conext MPPT 60 150 Solar Charge Controllers975-0720-01-01 3–25This manual is for use by qualified personnel onlyFig

Seite 122 - A Legacy USB-to

Device Configuration3–26 975-0720-01-01This manual is for use by qualified personnel onlySolar Input ConfigurationSolar Input Configuration allows you

Seite 123 - USB-to-Xanbus adapter drivers

Configuring Conext MPPT 80 600 and Conext MPPT 60 150 Solar Charge Controllers975-0720-01-01 3–27This manual is for use by qualified personnel onlyAdv

Seite 124 - Windows XP

Device Configuration3–28 975-0720-01-01This manual is for use by qualified personnel onlyConfiguring the Conext Automatic Generator StartThe following

Seite 125 - Windows 7

Configuring the Conext Automatic Generator Start975-0720-01-01 3–29This manual is for use by qualified personnel onlyGenerator ConfigurationGenerator

Seite 126

Device Configuration3–30 975-0720-01-01This manual is for use by qualified personnel onlyExercise Time Sets the time of day that the AGS exercises the

Seite 127 - Windows 8

Configuring the Conext Automatic Generator Start975-0720-01-01 3–31This manual is for use by qualified personnel onlyTrigger ConfigurationTrigger Conf

Seite 128

Device Configuration3–32 975-0720-01-01This manual is for use by qualified personnel onlyLow Battery Voltage Start(24 hr)Enables the AGS to start the

Seite 129

Configuring the Conext Automatic Generator Start975-0720-01-01 3–33This manual is for use by qualified personnel onlyMulti-Unit AGS ConfigurationAGS B

Seite 130 - Schneider Electric

Device Configuration3–34 975-0720-01-01This manual is for use by qualified personnel onlySaving and Restoring ConfigurationsSave Configuration allows