Software Release Notes10 975-0604-01-01 Revision A4. Updated grid/gen entry/exit/regulation voltage offsets in respect of grid/gen support voltage.5.
Software Release Notes975-0604-01-01 Revision A 1110. Changed the fault-set hysteresis to 0V for F48 (DC under voltage fault) to prevent premature fau
Software Release Notes12 975-0604-01-01 Revision A5. Fixed problem where system would lock up after multiple adjustments of support amps from 0 to 10
Software Release Notes975-0604-01-01 Revision A 13e) Vbulk and Vabs settings are now totally independent from each other on SCP.f) Minimum charge perc
Software Release Notes14 975-0604-01-01 Revision A31. Changed "FREQ" cmd so that it now accepts decimal frequency settings such as "55.
Software Release Notes975-0604-01-01 Revision A 159. Updated grid/gen entry/exit/regulation voltage offsets in respect of grid/gen support voltage.10.
Software Release Notes16 975-0604-01-01 Revision A16. Improved charge voltage regulation in a multiunit installation where more than one unit is charg
Software Release Notes975-0604-01-01 Revision A 173. Changed frequency hysteresis from 2hz to 0.5hz4. Changed minimum breaker size to 3A.5. Implemente
Software Release Notes18 975-0604-01-01 Revision Ad) 0Ahr battery capacity is deemed that there is no absorption exit current criteria and absorption
Software Release Notes975-0604-01-01 Revision A 1929. Changed "FREQ" cmd so that it now accepts decimal frequency settings such as "55.
Software Release Notes2 975-0604-01-01 Revision A865-1000 (Xantrex XW6048-NA)865-1000.01_03_00.BN0012Build Range: 865-1000.01_00_00.BN0028 — 865-1000.
Software Release Notes20 975-0604-01-01 Revision A865-1030 (Xantrex XW MPPT Charge Controller)865-1030.01_05_00.BN00061. The charge algorithm was modi
Software Release Notes975-0604-01-01 Revision A 212. Improvements were made to the Xantrex Xanbus library to make the device more robust on the CAN ne
Software Release Notes22 975-0604-01-01 Revision ASchneider Electric, the Schneider Electric logo, Xanbus and Xantrex are trademarks or registered tra
Software Release Notes975-0604-01-01 Revision A 33. Changed frequency hysteresis from 2hz to 0.5hz.4. Changed minimum breaker size to 3A.5. Implemente
Software Release Notes4 975-0604-01-01 Revision A12. Changed battery temperature compensation during charge from 10°C-40°C to 0°C-50°C13. Implemented
Software Release Notes975-0604-01-01 Revision A 5865-1005 (Xantrex XW4548-NA)865-1005.01_04_00.BN0015Build number range: 1.0.0BN10 — 1.4.0BN15Time ran
Software Release Notes6 975-0604-01-01 Revision A13. Fixed incorrect power calculation for AC Gen L1.14. Disabled SINEGEN sync functionality on hibern
Software Release Notes975-0604-01-01 Revision A 73. Implemented new charge algorithm. The differences from the previous implementation are:a) Bulk exi
Software Release Notes8 975-0604-01-01 Revision A16. Changed AC coupling frequency push limits down to -5Hz.17. Made phase_error and period_error limi
Software Release Notes975-0604-01-01 Revision A 910. Changed warning 70 into fault 70 ( phase configuration fault).11. Eliminated fault, warning and e