Tech Data Sheet D01688GB1 Fire Detection 5
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number D01688GB1 10 2012
© 2009 Schneider Electric. All rights reserved.
FXM 3NET panel external connections
Serial (RS485) communication with other FX panels (2 pcs)
Clean contact signal inputs (4 pcs), function configurable
Power supply outputs 24 VDC (2 pcs), short circuit protected, 2 A each
INFO communication
REPX-OB
or
MCOX-OB
or
ZLPX-IC
Master
controller
FX-MC2
Loop controller
FX-ALCA, FX-ALCB
0…2 pcs
Loop controller
FX-CLC
0…2 pcs
Output controller
FX-OCA
0…2 pcs
Input/output
controller
FX-IOC
0…2 pcs
Power supply
FX-PSA
Serial (RS232) communication with printer or maintenance tool (PC)
External communication (not in ZLPX-IC)
Fire Alarm Router Equipment (Alarm transmitter)
Fault Warning Router Equipment (Alarm transmitter)
Fire Alarm Output
Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each
Monitored relay outputs (4 pcs), max 500 mA each, function configurable
Battery 24 VDC (max 34 Ah)
Fault in Fire Alarm Router Equipment (Alarm transmitter)
Fault in Fault Warning Router Equipment (Alarm transmitter)
FX-ALCA: One addressable detection circuits, with 126 addresses
FX-ALCB: Two addressable detection circuits, each 126 addresses
FX-ALCA: One power supply outputs 24 VDC, short circuit protected, 500 mA
FX-ALCB: Two power supply outputs 24 VDC, short circuit protected, 500 mA each
Monitored output (Bells, sounders, beacon), 500 mA
Power supply output 24 VDC, short circuit protected, 500 mA
USB connection, maintenance tool (PC)
For each FX-CLC: 16 Conventional detection circuits, function configurable
Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable
Ethernet connection, INFO communication: Future option
Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX
Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable
230 VAC / 50 Hz / 80 VA
INFO communication
Note!
The maximum total load of the panel is 0.5 A in normal condition and 2.2 A in alarm condition.
The maximum number of ALCA, ALCB, CLC, IOC, OCA, REPX-OB, MCOX-OB and ZLPX-IC boards is 2.